If
[2] Logic AND
is selected, both signals must be activated
to perform the function.
Terminal
Bits 02/03/04
Function
0
0
Stop/Counterclockwise
0
1
Stop/Counterclockwise
1
0
Stop/Counterclockwise
1
1
Start/Clockwise
Table 8.7 [2] Logic AND
If
[3] Logic OR
is selected, activation of 1 signal activates
the function.
Terminal
Bits 02/03/04
Function
0
0
Stop/Counterclockwise
0
1
Start/Clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
Table 8.8 [3] Logic OR
The effect of control mode on the function of
parameter 8-55 Set-up Select
and
parameter 8-56 Preset
Reference Select
:
If
[0] Digital input
is selected, the terminals control the set-
up and preset reference functions.
Terminal
Bits 00/01, 13/14
Function
Msb
Lsb
Msb
Lsb
Preset reference set-
up number
0
0
0
0
1
0
0
0
1
1
0
0
1
0
1
0
0
1
1
1
0
1
0
0
2
0
1
0
1
2
0
1
1
0
2
0
1
1
1
2
1
0
0
0
3
1
0
0
1
3
1
0
1
0
3
1
0
1
1
3
1
1
0
0
4
1
1
0
1
4
1
1
1
0
4
1
1
1
1
4
Table 8.9 [0] Digital Input
If
[1] Serial communication
is selected, commands are
activated only when given via serial communication.
Terminal
Bits 00/01, 13/14
Function
Msb
Lsb
Msb
Lsb
Preset reference set-
up number
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
1
0
1
0
1
2
0
1
1
0
3
0
1
1
1
4
1
0
0
0
1
1
0
0
1
2
1
0
1
0
3
1
0
1
1
4
1
1
0
0
1
1
1
0
1
2
1
1
1
0
3
1
1
1
1
4
Table 8.10 [1] Serial Communication
If
[2] Logic AND
is selected, both signals must be activated
to perform the function.
Terminal
Bits 00/01, 13/14
Function
Msb
Lsb
Msb
Lsb
Preset reference set-
up number
0
0
0
0
1
0
0
0
1
1
0
0
1
0
1
0
0
1
1
1
0
1
0
0
1
0
1
0
1
2
0
1
1
0
1
0
1
1
1
2
1
0
0
0
1
1
0
0
1
1
1
0
1
0
3
1
0
1
1
3
1
1
0
0
1
1
1
0
1
2
1
1
1
0
3
1
1
1
1
4
Table 8.11 [2] Logic AND
Troubleshooting
Programming Guide
MG06G102
Danfoss A/S © 04/2017 All rights reserved.
49
8