Parameter
Default value
2 set-up
Change during
operation
Conversion
index
Data type
Parameter 12-06 Name Servers
0
1 set-up
TRUE
–
Oct. string 4
Parameter 12-07 Domain Name
0
1 set-up
TRUE
–
Visible string 48
Parameter 12-08 Host Name
0
1 set-up
TRUE
–
Visible string 48
Parameter 12-09 Physical Address
0
1 set-up
TRUE
–
Visible string 17
Parameter 12-10 Link Status
[0] No Link
All set-ups
TRUE
–
Uint8
–
All set-ups
TRUE
–
Time diff. w/date
Parameter 12-12 Auto Negotiation
[1] On
1 set-up
TRUE
–
Uint8
Parameter 12-13 Link Speed
[0] None
1 set-up
TRUE
–
Uint8
Parameter 12-14 Link Duplex
[1] Full Duplex
1 set-up
TRUE
–
Uint8
Parameter 12-80 FTP Server
[0] Disabled
1 set-up
TRUE
–
Uint8
Parameter 12-81 HTTP Server
[0] Disabled
1 set-up
TRUE
–
Uint8
Parameter 12-82 SMTP Service
[0] Disabled
1 set-up
TRUE
–
Uint8
Parameter 12-89 Transparent Socket Channel
Port
–
1 set-up
TRUE
0
Uint16
Parameter 12-90 Cable Diagnostic
[0] Disabled
1 set-up
TRUE
–
Uint8
Parameter 12-91 Auto Cross Over
[1] Enabled
1 set-up
TRUE
–
Uint8
Parameter 12-92 IGMP Snooping
[1] Enabled
1 set-up
TRUE
–
Uint8
Parameter 12-93 Cable Error Length
0
1 set-up
TRUE
0
Uint16
Parameter 12-94 Broadcast Storm Protection
-1%
1 set-up
TRUE
0
Int8
Parameter 12-95 Inactivity timeout
[0] Broadcast only
1 set-up
TRUE
–
Uint8
Parameter 12-96 Port Config
–
1 set-up
TRUE
–
Uint8
Parameter 12-98 Interface Counters
4000
All set-ups
TRUE
0
Uint32
Parameter 12-99 Media Counters
0
All set-ups
TRUE
0
Uint32
Table 6.6 PROFINET-specific Parameter List
6.5.5 Conversion
The various attributes of each parameter are shown in
factory setting. Parameter values are transferred as whole
numbers only. Conversion factors are therefore used to
transfer decimals.
A conversion factor of 0.1 means that the value transferred
is multiplied by 0.1. The value 100 is therefore read as 10.0.
Examples:
0 s
⇒
conversion index 0
0.00 s
⇒
conversion index -2
0 ms
⇒
conversion index -3
0.00 ms
⇒
conversion index -5
Conversion index
Conversion factor
100
1
75
3600000
74
3600
70
60
67
1/60
6
1000000
5
100000
4
10000
3
1000
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
-5
0.00001
-6
0.000001
Table 6.7 Conversion Table