Reference site set in
parameter 3-13 Reference Site
Local reference active [120]
Remote reference active [121]
Reference site: Linked to Hand/ Auto
–
–
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
Table 26: 5-30 Digital Outputs - 2
Option
Function
[121]
Remote ref active
Output is high when
parameter 3-13 Reference Site
=
[1] Remote
or
[0] Linked to hand/auto
while the
LCP is in auto-on mode. See
.
[122]
No alarm
Output is high when no alarm is present.
[123]
Start command ac-
tive
Output is high when there is an active start command (that is via digital input bus connection, hand-
on, or auto-on), and no stop or start command is active.
[124]
Running reverse
Output is high when the drive runs counterclockwise (the logical product of the status bits running
AND reverse).
[125]
Drive in hand
mode
Output is high when the drive is in hand-on mode (as indicated by the LED light above [Hand On]).
[126]
Drive in auto mode
Output is high when the drive is in auto-on mode (as indicated by the LED light above [Auto On]).
[151]
ATEX ETR cur.
alarm
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
. If
Alarm 164 ATEX ETR cur.lim.alarm
is active, the output is 1.
[152]
ATEX ETR freq.
alarm
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
. If
Alarm 166 ATEX ETR freq.lim.alarm
is active, the output is 1.
[153]
ATEX ETR cur.
warning
[154]
ATEX ETR freq.
warning
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
. If
Warning 165, ATEX ETR freq.lim.warning
is active, the output is 1.
[180]
Clock fault
[181]
Prev. maintenance
[188]
AHF capacitor con-
nect
The capacitors are turned on at 20% (hysteresis of 50% gives an interval of 10– 30%). The capacitors
are disconnected below 10%. The off delay is 10 s and restarts if the nominal power goes above 10%
during the delay.
Parameter 5-80 AHF Cap Reconnect Delay
is used to guarantee a minimum off time
for the capacitors.
[189]
External fan control
The internal logics for the internal fan control is transferred to this output to make it possible to con-
trol an external fan (relevant for hp duct cooling).
[190]
Safe function ac-
tive
[191]
Safe opt. reset req.
[192]
RS Flipflop 0
See
parameter group 13-1* Comparators
.
[193]
RS Flipflop 1
See
parameter group 13-1* Comparators
.
[194]
RS Flipflop 2
See
parameter group 13-1* Comparators
.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
36 | Danfoss A/S © 2020.01