Option
Function
[51]
External inter-
lock
This function makes it possible to give an external fault to the drive. This fault is treated in the same way
as an internally generated alarm.
[55]
DigiPot in-
crease
Increase signal to the digital potentiometer function described in
parameter group 3-9* Digital Pot. Meter
.
[56]
DigiPot De-
crease
Decrease signal to the digital potentiometer function described in
parameter group 3-9* Digital Pot. Me-
ter
.
[57]
DigiPot Clear
Clears the digital potentiometer reference described in
parameter group 3-9* Digital Pot. Mete
r.
[60]
Counter A
(Terminal 29 or 33 only). Input for increment counting in the SLC counter.
[61]
Counter A
(Terminal 29 or 33 only). Input for decrement counting in the SLC counter.
[62]
Reset Counter
A
Input for reset of counter A.
[63]
Counter B
(Terminal 29 or 33 only). Input for increment counting in the SLC counter.
[64]
Counter B
(Terminal 29 or 33 only). Input for decrement counting in the SLC counter.
[65]
Reset Counter
B
Input for reset of counter B.
[70]
Mech. Brake
Feedback
Brake feedback for hoisting applications: Set
parameter 1-01 Motor Control Principle
to
[3] Flux w/ motor
feedback
; set
parameter 1-72 Start Function
to
[6] Hoist mech brake Ref
.
[71]
Mech. Brake
Feedback inv.
Inverted brake feedback for hoisting applications.
[72]
PID error in-
verse
When enabled, this option inverts the resulting error from the process PID controller. Available only if
parameter 1-00 Configuration Mode
is set to
[6] Surface Winder
,
[7] Extended PID Speed OL
, or
[8] Extended
PID Speed CL
.
[73]
PID reset I-part
When enabled, this option resets the I-part of the process PID controller. Equivalent to
parameter 7-40
Process PID I-part Reset
. Available only if
parameter 1-00 Configuration Mode
is set to
[6] Surface Winder
,
[7]
Extended PID Speed OL
, or
[8] Extended PID Speed CL
.
[74]
PID enable
Enables the extended process PID controller. Equivalent to
parameter 7-50 Process PID Extended PID
.
Available only if
parameter 1-00 Configuration Mode
is set to
[7] Extended PID Speed OL
or
[8] Extended PID
Speed CL
.
[80]
PTC Card 1
All digital inputs can be set to
[80] PTC Card 1
. However, only 1 digital input must be set to this option.
[91]
PROFIdrive
OFF2
The functionality is the same as the corresponding control word bit of the PROFIBUS/PROFINET option.
[92]
PROFIdrive
OFF3
The functionality is the same as the corresponding control word bit of the PROFIBUS/PROFINET option.
[94]
Light Load De-
tection
Light-load detection is a feature for lift application to ensure that the lift runs in the evacuation direction
which requires the least energy (UPS capacity), during an emergency. See
parameter 30-25 Light Load De-
lay [s]
,
parameter 30-26 Delay Before Measurements
,
parameter 30-27 Light Load Speed [%]
,
parameter 30-28
Evacuation Speed [%]
, and
parameter 30-29 Ramp Time
for light-load detection configurations.
NOTICE
Flying start overrules light load detection.