Option
Function
[109]
Enable Vir.Mas-
ter
NOTICE
This option is available only with IMC software version 48.XX.
Enable signal for the virtual master function. Only applicable when option
[10] Synchronization
is selec-
ted in
parameter 1-00 Configuration Mode
.
[110]
Start homing
NOTICE
This option is available only with IMC software version 48.XX.
Starts the homing function selected in
parameter 17-80 Homing Function
. Must remain high until homing
is done, otherwise homing is aborted.
[111]
Activate touch
NOTICE
This option is available only with IMC software version 48.XX.
Activates the monitoring of the touch sensor input.
[112]
Relative posi-
tion
NOTICE
This option is available only with IMC software version 48.XX.
This option selects between absolute and relative positioning. The option is valid for the next position-
ing command.
[113]
Enable refer-
ence
NOTICE
This option is available only with IMC software version 48.XX.
Positioning mode: The drive activates the selected positioning type and target and starts the motion to-
wards the new target. The motion starts either immediately or when active positioning is completed, de-
pending on settings of
parameter 17-90 Absolute Position Mode
and
parameter 17-91 Relative Position
Mode
. Synchronization mode: High signal locks the actual follower position to the actual master position.
The follower starts and catches up with the master. Low signal stops the synchronization and the follow-
er makes a controlled stop.
[114]
Sync. to Pos.
Mode
NOTICE
This option is available only with IMC software version 48.XX.
Select positioning in synchronization mode.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
24 | Danfoss A/S © 2020.01