Option
Function
[9]
Latched start
If a pulse is applied for minimum 2 ms, the motor starts. The motor stops when stop inverse is activated,
or a reset command (via DI) is given.
[10]
Reversing
(Default digital input 19). Change the direction of motor shaft rotation. Select logic 1 to reverse. The re-
versing signal only changes the direction of rotation. It does not activate the start function. Select both
directions in
parameter 4-10 Motor Speed Direction
. The function is not active in process closed loop.
[11]
Start reversing
Used for start/stop and for reversing on the same wire. Signals on start are not allowed at the same time.
[12]
Enable start
forward
Disengages the counterclockwise movement and allows clockwise direction.
[13]
Enable start re-
verse
Disengages the clockwise movement and allows counterclockwise direction.
[14]
Jog
(Default digital input 29): Activate jog speed. See
parameter 3-11 Jog Speed [Hz]
.
[15]
Preset refer-
ence on
Shifts between external reference and preset reference. It is assumed that
[1] External/preset
has been se-
lected in
parameter 3-04 Reference Function
. Logic 0 = external reference active; logic 1 = 1 of the 8 preset
references is active.
[16]
Preset ref bit 0
Preset reference bit 0, 1, and 2 enable a choice between 1 of the 8 preset references according to
.
[17]
Preset ref bit 1
Same as
[16] Preset ref bit 0
.
[18]
Preset ref bit 2
Same as
[16] Preset ref bit 0
.
Table 9: Preset Reference Bit
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Table 10: 5-10 Digital Inputs - 2
Option
Function
[19]
Freeze
ref
Freezes the actual reference, which is now the point of enable/condition to be used for
[21] Speed up
and
[22]
Speed down
. If speed up/speed down is used, the speed change always follows ramp 2 (
parameter 3-51 Ramp 2
Ramp Up Time
and
parameter 3-52 Ramp 2 Ramp Down Time
) in the range 0–
parameter 3-03 Maximum Reference
.
Parameter Setup