ID
Parameter Name
A230.x
Setting range
Factory
Unit
Own
settings
11035
Infl. - max.
1, 4
-9.9 ... 9.9
-2.0
-||-
2
-9.9 ... 9.9
0.0
11036
Infl. - min.
1, 4
-9.9 ... 9.9
0.0
-||-
2
-9.9 ... 9.9
2.0
11037
Adapt. time
1, 4
OFF, 1 ... 50
25
Sec
-||-
2
OFF, 1 ... 50
OFF
Sec
11040
P post-run
1, 2, 4
0 ... 99
3
Min
11050
P demand
1, 2, 4
OFF ; ON
OFF
11052
DHW priority
1, 4
OFF ; ON
OFF
11057
Infl. - max.
1
0.0 ... 9.9
0.0
11060
Limit
2
-20 ... 80
5
°C
11061
Adapt. time
2
OFF, 1 ... 50
OFF
Sec
11062
Infl. - max.
2
-9.9 ... 9.9
0.0
11063
Infl. - min.
2
-9.9 ... 9.9
0.0
11064
Limit
2
-20 ... 80
25
°C
11065
Adapt. time
2
OFF, 1 ... 50
OFF
Sec
11066
Infl. - max.
2
-9.9 ... 9.9
0.0
11067
Infl. - min.
2
-9.9 ... 9.9
0.0
11070
P cool T
2
5 ... 60
25
°C
11077
P frost T
1, 4
OFF, -10 ... 20
2
°C
11078
P heat T
1, 4
5 ... 40
20
°C
11079
Max. flow T
1, 4
10 ... 110
60
°C
11080
Delay
1, 4
5 ... 250
30
Sec
11081
Filter constant
1
1 ... 50
10
11084
Ext. signal
2
OFF ; ON
OFF
11085
Priority
1, 4
OFF ; ON
OFF
11092
Standby T
2
5 ... 40
30
°C
11093
Frost pr. T
1, 4
5 ... 40
10
°C
11099
Limit
1
0.0 ... 35.0
10.0
m/s
11109
Input type
1, 2, 4
OFF ; IM1 ; IM2 ;
IM3 ; IM4 ; EM1 ;
EM2 ; EM3 ; EM4
; EM5
OFF
11111
Limit
2
0.0 ... 999.9
999.9
11112
Adapt. time
1, 2, 4
OFF, 1 ... 50
OFF
Sec
11113
Filter constant
1, 2, 4
1 ... 50
10
11114
Pulse
1, 2, 4
OFF, 1 ... 9999
OFF
11115
Units
1, 2, 4
ml, l/h ; l, l/h ; ml,
m3/h ; l, m3/h ;
Wh, kW ; kWh,
kW ; kWh, MW
; MWh, MW ;
MWh, GW ; GWh,
GW
ml, l/h
VI.LG.H4.02
© Danfoss | 2017.05 | 155
Operating Guide ECL Comfort 210/296/310, application A230