7.7 Parameter ID overview
A230x —
x
refers to the subtypes listed in the column.
ID
Parameter Name
A230.x
Setting range
Factory
Unit
Own
settings
10512
Prog. execution
1, 4
OFF ; ON
OFF
10514
Max. pwr. failure
1, 4
5 ... 3000
30
Min
10903
Ramp X5-X6
1, 4
OFF, 1 ... 20
5
10904
Ramp X7-X8
1, 4
OFF, 1 ... 20
5
10912
Appl. continue
1, 4
OFF ; ON
OFF
10913
After power fail.
1, 4
STOP ; START
OFF
10930
X1
1, 4
0 ... 1200
0
h
10931
X2
1, 4
0 ... 1200
0
h
10932
X3
1, 4
0 ... 1200
0
h
10933
X4
1, 4
0 ... 1200
0
h
10934
X5
1, 4
0 ... 1200
0
h
10935
X6
1, 4
0 ... 1200
360
h
10936
X7
1, 4
0 ... 1200
720
h
10937
X8
1, 4
0 ... 1200
1080
h
11004
Desired T
1, 4
5 ... 150
50
°C
11010
ECA addr.
1, 2, 4
OFF ; A ; B
OFF
11011
Auto saving
1, 4
OFF, -29 ... 10
-15
°C
11012
Boost
1, 4
OFF, 1 ... 99
OFF
%
11013
Ramp
1, 4
OFF, 1 ... 99
OFF
Min
11014
Optimizer
1, 4
OFF, 10 ... 59
OFF
11015
Adapt. time
1, 2, 4
OFF, 1 ... 50
OFF
Sec
11017
Demand offset
1, 4
OFF, 1 ... 20
OFF
K
-||-
2
-20 ... -1, OFF
OFF
K
11018
Des. T comfort
2
-30.0 ... 60.0
7.5
°C
11019
Des. T saving
2
-30.0 ... 60.0
25.0
°C
11020
Based on
1, 4
OUT ; ROOM
OUT
11021
Total stop
1, 4
OFF ; ON
OFF
11022
P exercise
1, 2, 4
OFF ; ON
ON
11023
M exercise
1, 2, 4
OFF ; ON
OFF
11024
Actuator
1, 2, 4
ABV ; GEAR
GEAR
11026
Pre-stop
1, 4
OFF ; ON
ON
11028
Con. T, ret. T lim.
1, 4
10 ... 110
70
°C
11029
DHW, ret. T limit
1, 4
OFF, 10 ... 110
OFF
°C
11030
Limit
2
-20 ... 80
20
°C
11031
High T out X1
1, 4
-60 ... 20
15
°C
11032
Low limit Y1
1, 4
10 ... 150
50
°C
11033
Low T out X2
1, 4
-60 ... 20
-15
°C
11034
High limit Y2
1, 4
10 ... 150
60
°C
154 | © Danfoss | 2017.05
VI.LG.H4.02
Operating Guide ECL Comfort 210/296/310, application A230