MENU > Settings > Wind influence
Wind actual
The actual wind speed is indicated by the unit ‘m/s’ (meter per second).
Push the dial to see the graph and enter the value sets for the input
voltage (2 and 10 volt) and displayed wind speed.
Wind speed:
0.0 ... 75.0 m/s
Fixed voltage settings:
2 V and 10 V
Factory settings:
(2 , 5.0) and (10 , 25.0)
This means that the ‘Wind actual’ is 5.0 m/s at 2.0 volt and 25.0
m/s at 10 volt.
Typically, the higher the voltage, the higher the displayed wind
speed.
Example: Relationship between input voltage and displayed wind speed
Wind speed (m/s)
Volt
This example shows that 2 volt correspond to 5.0 m/s and 10 volt correspond
to 25.0 m/s.
MENU > Settings > Wind influence
Limit
1x099
If the wind speed exceeds the set value, the desired flow temperature will
be increased.
See Appendix “Parameter ID overview”
VI.LG.H4.02
© Danfoss | 2017.05 | 83
Operating Guide ECL Comfort 210/296/310, application A230