MENU > Settings > Flow temperature
Desired T (Desired flow temperature)
1x004
When the ECL Comfort is in override mode, type "Const. T", the desired flow
temperature can be set.
A "Const. T" related return temperature limitation can also be set. See MENU
> Settings > Return limit > 'Con. T, ret. T lim.'
See Appendix “Parameter ID overview”
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
The "Desired T" value can be influenced by:
•
temp. max.
•
temp. min.
•
room temp. limit
•
return temp. limit
•
flow / power limit
MENU > Settings > Flow temperature
Des. T Comfort
1x018
Setting of desired flow temperature when the ECL controller is in comfort
mode.
See Appendix “Parameter ID overview”
This setting has no influence if the controller receives an external value
for the desired flow temperature.
MENU > Settings > Flow temperature
Des. T Saving
1x019
Setting of desired flow temperature when the ECL controller is in saving
mode.
See Appendix “Parameter ID overview”
This setting has no influence if the controller receives an external value
for the desired flow temperature.
MENU > Settings > Flow temperature
Ext. signal
1x084
See Appendix “Parameter ID overview”
OFF:
The desired flow temperature is set in the controller.
ON:
The desired flow temperature is applied as a 0 - 10 V
signal.
See 'Ext. desired T'. The value is an externally set desired flow
temperature.
66 | © Danfoss | 2017.05
VI.LG.H4.02
Operating Guide ECL Comfort 210/296/310, application A230