MENU > Settings > Alarm
Alarm low
1x615
When the measured value gets lower than the set value, the alarm will be
activated.
See Appendix “Parameter ID overview”
Value:
Set the alarm value
MENU > Settings > Alarm
Alarm time-out
1x617
The alarm is activated when the alarm reason has been present for a longer
time (in seconds) than the set value.
See Appendix “Parameter ID overview”
Value:
Set the alarm time-out
MENU > Settings > Alarm
Upper difference
1x147
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay'.
See Appendix “Parameter ID overview”
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
Upper difference
X
=
Time
Y
=
Temperature
# 1 #
=
Upper difference
# 2 #
=
Desired flow temperature
VI.LG.H4.02
© Danfoss | 2017.05 | 113
Operating Guide ECL Comfort 210/296/310, application A230