MENU > Settings > Flow / power limit
Actual (actual flow or power)
The value is the actual flow or power based on the signal from flow / energy
meter.
MENU > Settings > Flow / power limit
Limit (limitation value)
1x111
This value is in some applications a calculated limitation value, based on the
actual outdoor temperature.
In other applications the value is a selectable limitation value.
See Appendix “Parameter ID overview”
MENU > Settings > Flow / power limit
Adapt. time (adaptation time)
1x112
Controls how fast the flow / power limitation adapts to the desired
limitation.
See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor
value:
The desired temperature is adapted quickly.
Major
value:
The desired temperature is adapted slowly.
If the ‘Adapt. time’ is too low, there is a risk of unstable control.
MENU > Settings > Flow / power limit
Filter constant
1x113
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
See Appendix “Parameter ID overview”
Minor
value:
Lower dampening
Major
value:
Higher dampening
MENU > Settings > Flow / power limit
Pulse
1x114
Set the value of the pulses from the flow / energy meter.
See Appendix “Parameter ID overview”
OFF:
No input.
1 ... 9999:
Pulse value.
Example :
One pulse can represent a number of litres (from a flow meter)
or a number of kWh (from a energy meter).
VI.LG.H4.02
© Danfoss | 2017.05 | 79
Operating Guide ECL Comfort 210/296/310, application A230