5.9 Compensation 1
The desired flow temperature can be influenced by a compensation
temperature, measured by S1.
This application contains 2 compensation temperature limits:
Compensation 1 (Comp. 1) and Compensation 2 (Comp. 2).
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Compensation 1
Limit (compensation temp., 1. point)
1x060
Set the compensation temperature limit point 1.
See Appendix “Parameter ID overview”
When the compensation temperature measured by Sx falls below
or gets higher than the set value, the controller automatically
changes the desired flow / duct temperature. The influence is set
in 'Infl. - max.' and 'Infl. - min.'.
Influence
Temp. Sx
Compensation 1
MENU > Settings > Compensation 1
Adapt. time (adaptation time)
1x061
Controls how fast the compensation / surface temperature influences the
desired flow / duct temperature.
See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor
value:
The desired flow / duct temperature is adapted quickly.
Major
value:
The desired flow / duct temperature is adapted slowly.
Value:
Set the adaptation time
The adaptation function can correct the desired flow / duct
temperature with max. 8 K.