MENU > Settings > Room limit
Infl. - min. (room temp. limitation, min.)
1x183
Determines how much the desired flow temperature will be influenced
(increased) if the actual room temperature is lower than the desired room
temperature (P control).
See Appendix “Parameter ID overview”
9.9:
Maximum influence
5.0:
Medium influence
2.0:
Minor influence
0.0:
No influence
Example
The actual room temperature is 2 degrees too low.
The ‘Infl. - min.’ is set to 4.0.
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Result:
The desired flow temperature is changed by (2 x 4.0 x 1.8)
14.4 degrees.
In application subtypes, where a heat curve slope value is
not
present,
the heat curve slope value is set to 1:
Result:
The desired flow temperature is changed by (2 x 4.0 x 1):
8.0 degrees.
70 | © Danfoss | 2017.05
VI.LG.H4.02
Operating Guide ECL Comfort 210/296/310, application A230