
MENU > Settings > Return limit
Adapt. time (adaptation time)
1x037
Controls how fast the return temperature adapts to the desired return
temperature limit (Integration control).
See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor
value:
The desired temperature is adapted quickly.
Major
value:
The desired temperature is adapted slowly.
The adaptation function can correct the desired flow temperature
with max. 8 K.
MENU > Settings > Return limit
Priority (priority for return temp. limitation)
1x085
Choose whether the return temperature limitation should overrule the set
min. flow temperature ‘Temp. min.’ .
See Appendix “Parameter ID overview”
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
If you have a DHW application:
Please also see ‘Parallel operation’ (ID 11043).
If you have a DHW application:
When dependent parallel operation is in function:
•
Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
•
Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.
76 | © Danfoss | 2017.05
VI.LG.H4.02
Operating Guide ECL Comfort 210/296/310, application A230