MENU > Settings > Compensation 1
Infl. - max. (compensation temp., 1. point)
1x062
Determines how much the desired flow / duct temperature will be influenced
if the compensation temperature is higher than the set limit.
See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the
compensation temperature gets above the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the
compensation temperature gets above the set limit.
Example
The limit value is set to 5 °C.
‘Infl. max.’ is set to -1.5.
The actual compensation temperature is 7°C (2 degrees above the
limit value).
Result:
The desired flow / duct temperature is changed by -1.5 x 2 = -3.0
degrees.
MENU > Settings > Compensation 1
Infl. - min. (compensation temp., 1. point)
1x063
Determines how much the desired flow / duct temperature will be influenced
if the compensation temperature is lower than the set limit.
See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the
compensation temperature gets below the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the
compensation temperature gets below the set limit.
Example
The limit value is set to 5 °C.
‘Infl. min.’ is set to 2.5.
The actual compensation temperature is 2°C (3 degrees below the
limit value).
Result:
The desired flow / duct temperature is changed by 2.5 x 3 = 7.5
degrees.
96 | © Danfoss | 2017.05
VI.LG.H4.02
Operating Guide ECL Comfort 210/296/310, application A230