Definitions
Limitation temperature
Temperature that influences the desired flow / balance temperature.
Pt 1000 sensor
All sensors used with the ECL Comfort controller are based on the Pt 1000 type. The
resistance is 1000 ohm at 0 °C and it changes with approx. 3.9 ohm / degree.
Optimization
The controller optimizes the start / stop time of the scheduled temperature periods.
Based on the outdoor temperature, the controller automatically calculates when to start
/ stop in order to reach the comfort temperature at the set time. The lower the outdoor
temperature, the earlier the start time. During optimization the comfort / setback
symbol will blink.
Return temperature
The temperature measured in the return can influence the desired flow temperature.
Room temperature sensor
Temperature sensor placed in the room (reference room, typically the living room) where
the temperature is to be controlled.
Room temperature
Temperature measured by the room temperature sensor, room panel or remote
control. The room temperature can only be controlled directly if a room temperature is
measured. The room temperature can influence the desired flow temperature.
Schedule
Schedule for periods with comfort and setback temperatures. The schedule can be made
individually for each week day and it consists of 2 comfort periods per day.
Setback temperature
Temperature maintained in the heating / DHW circuit during setback temperature
periods.
Time bar
The time bars illustrate scheduled periods with comfort temperature.
Weather compensation
Flow temperature control based on the outdoor temperature. The control is related to a
user-defined heat curve.
The definitions apply to the Comfort 110 series. Consequently, you might come across
expressions that are not mentioned in your guide.