Maintenance
2 sec.
Enter the maintenance menus.
Date - time
1000
It is only necessary to set the correct date and time in connection with the first use of the
ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter
on
Adapting the ECL Comfort 110 controller).
Flow temp. (flow temperature control)
2000
Heat curve
The ECL Comfort 110 controls the heating system according to the calculated flow
temperature under the influence of the return and / or room temperature.
The desired flow temperature is defined by 5 settings: ‘Temp. max.’, ‘Temp. min.’, ‘Slope’,
‘Displace’, and ‘Knee point’.
Desired flow temperature
-20
-10
0
10
20
-30
20
30
40
50
60
70
80
90
100
110
10
[°C]
[°C]
Heat curve
‘Slope’
‘Temp. max.’
‘Displace’
‘Knee point’
‘Temp. min.’
Outdoor temp.
The calculated flow temperature can be influenced by connected sensors, ‘Boost’ and ‘Ramp’
etc.