Maintenance
P1 heat T (heat demand)
7078
Setting range
Factory setting
5 ... 40 °C
20 °C
When the desired flow temperature is above the set temperature in ‘P1 heat T’, the controller
automatically switches ON the circulation pump to meet the heat demand.
5 ... 40: The circulation pump is ON above the set value.
The valve is fully closed as long as the pump is not switched on.
Standby T (standby temperature)
7093
Setting range
Factory setting
5 ... 40 °C
10 °C
Set the desired flow temperature at standby (e.g. during total stop).
5 ... 40: Desired standby flow temperature.
Ext. (external override)
7141
Setting range
Factory setting
OFF / SETBACK / COMFORT
OFF
Choose mode for ‘Ext.’ (external override).
The override can be activated for setback or comfort mode. For override, the controller
mode must be AUTO (scheduled operation).
OFF:
The controller's schedule is not overridden.
SETBACK:
The controller is in setback mode when terminals 11 and 12
are short-circuited.
COMFORT:
The controller is in comfort mode when terminals 11 and 12
are short-circuited.