This limitation is based on a PI regulation where P (Gain) responds quickly to deviations
and I (Intgr. time) responds slower and over time removes the small offsets between the
desired and actual values. This is done by changing the desired flow temperature.
Intgr. time (time constant for room temp.)
3015
Setting range
Factory setting
OFF / 1 ... 50
OFF
Controls how fast the room temperature adapts to the desired room temperature (I control).
OFF: The control function is not influenced by the ‘Intgr. time’.
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
Gain - max. (room temp. limitation, max.)
3182
Setting range
Factory setting
-9.9 ... 0.0
-4.0
Determines how much the flow temperature will be influenced (decreased) if the room temperature is
higher than the desired room temperature (P control).
-9.9: The room temperature has a big influence.
0.0:
The room temperature has no influence.
Gain - min. (room temp. limitation, min.)
3183
Setting range
Factory setting
0.0 ... 9.9
0.0
Determines how much the flow temperature will be influenced (increased) if the room temperature is
lower than the desired room temperature (P control).
0.0:
The room temperature has no influence.
9.9:
The room temperature has a big influence.