VI.KT.G6.02
32 | © Danfoss | 2016.05
Maintenance
0:
The controller works as slave. The slave receives information about the
outdoor temperature (S1), system time, and signal for DHW demand in
the master.
1 ... 9: The controller works as slave. The slave receives information about
the outdoor temperature (S1), system time, and signal for DHW
demand in themaster. The slave sends information about the desired
flow temperature to the master.
10 ... 14: Not used.
15:
The controller is master. The master sends information about the
outdoor temperature (S1) and system time. The ECL BUS is active and
connected ECAs are powered.
The ECL Comfort controllers can be connected via the ECL BUS to perform a larger
system. The controller, which is physically connected with the outdoor temperature
sensor, is the master of the entire system and must have the address 15.
Each slave must be configured with its own address (1 ... 9).
However, more slaves can have the address 0 if they only have to receive information
about outdoor temperature and system time.
Type 7600
Setting range
Factory setting
116 / 130
130
Use this setting to change your application or restore the factory settings.
116: Constant temperature control of DHW circuit.
130: Weather compensated control of heating and boiler systems.
Select the desired application type.
5 sec.
Start the chosen application.
Factory settings are restored. All personal settings will be deleted. It is recommended to
make a note of your personal settings in the ‘Settings overview’ for future use.
The application can not be changed from 116 to 130 or vice versa if the ECL Comfort 110 is
pre-programmed from the substation-builder.