VI.KT.G6.02 © Danfoss | 2016.05 | 23
Maintenance
Total stop
5021
Setting range
Factory setting
ON / OFF
OFF
Decide whether you want a total stop during the setback temperature period.
ON:
The desired system temperature is lowered to ‘Standby T’ (line 7093).
‘Temp. min.’ (line 2177) is overruled.
Desired system temp. °C
‘Standby T’
Time
OFF: No total stop
Desired system temp. °C
‘Standby T’
Time
S1 T filter (outdoor temp. filter)
5081
Setting range
Factory setting
1 ... 200
100
Dampens the measured outdoor temperatures by the set factor.
1:
Fast (low filter constant)
200: Slow (high filter constant)