background image

If oil return continues to perform poorly, further
investigation of the piping design is required.

• In all cases, the application limits of the compressor
must be respected; moreover, high superheat
values lead to high discharge temperatures and
decrease compressor capacity. The maximum
discharge temperature is 130°C: operating ata
higher temperature may result in refrigerant
decomposition.

• Under steady-state operating conditions, check
refrigerant piping or capillary tubes for abnormal
vibrations (refrigeration line movement in excess
of 1.5 mm necessitates corrective actions, pipe
brackets, etc.).

• Ensure that refrigerant flow through the liquid
line sight glass (when mounted) is adequate and
that operating temperatures correspond with
system specifications.

• When needed, refrigerant may be added in the
liquid phase, carefully throttling the refrigerant on
the low-pressure side and as far as possible from
the compressor.The compressor must be operating
during this process.

Do not overcharge the system.

11 - Troubleshooting

• 

Compressor failure to start:

verify that the

compressor is hooked up to the power supply;
check the power lead connections and all suitable
capacitors on single-phase models. If these
verifications reveal no abnormality, control the
motor windings with an ohmmeter.
Note: when the internal motor protector has tripped
out, it may take up to several hours to reset and
restart the compressor.

• 

Compressor failure to build up pressure:

check to make sure that all bypass valves in the
system have not been opened. Also check that all
solenoid valves are in their proper position. If the
internal pressure relief valve is open, the compressor
sump will be warm and the compressor will trip
out on the motor protector. If this happens, it may
take up to 2 or 3 hours to reset and automatically
restart the compressor.

• 

Abnormal running noise on the system:

- Ensure the absence of any liquid flood-back

to the compressor by means of measuring
the return gas superheat and compressor sump
temperature. The sump should be at least 10K
above the saturated suction temperature under
steady-state operating conditions.

- Check that the fans are running free and without

vibration.

• 

The high-pressure switch trips out:

check

condenser operations (condenser cleanliness,
fan operations, etc.). If above check out OK,
the problem may be due to either refrigerant
overcharging or the presence of a non-condensable
(e.g. air, moisture) in the circuit.

• 

The low-pressure switch trips out:

check

evaporator operations (coil cleanliness, fan
operations, water flow, water filter, etc.), liquid
refrigerant flow and pressure drops (solenoid valve,
filter dryer, expansion valve, etc.), refrigerant charge.

• 

Low refrigerant charge:

the correct refrigerant

charge is given by the liquid sight glass indication,
the condenser delta T in relation to the refrigerant
pressure tables (pressure-temperature), the
superheat and the sub-cooling, etc. (if additional
charge is deemed necessary, refer to the «Filling
the system» section).

• Compressor maximum short cycling:

there

must be a minimum delay of five minutes between
two compressor starts. DCC recommends the
compressor should run at least two minutes after
each start, and between each stop and start must
be three minutes standstill. Only during pump
down cycle, the compressor may run much shorter
until the pumpdown pressure has been reached
or when safety devices will prohibit compressor
further operation.

12 - Maintenance

• Proper operations and maintenance of the
condensing units serve to prevent against
system-related problems. The following preventive
maintenance checks, to be performed at regular
intervals, are highly recommended:

- Control operating conditions (evaporating

temperature, condensing temperature,
compressor discharge temperature, temperature
difference on heat exchangers, superheat,
sub-cooling). These conditions must always
remain within compressor operation limits.

- Verify that safety devices are operational and

properly set.

- Check the compressor oil level and quality; this

step may include an acid test, humidity check,
spectrometer analysis, etc. whenever the oil
becomes discolored.

- Ensure that the circuit is leak tight.

- Verify the proper operation of heat exchangers

and, if necessary, clean them.

- Check that the fans are running free (without

vibration) and current draw on the compressor
motor as well as proper voltage balance
between phases.

- Change the filter dryer when necessary.

- Check that all electrical connections are still

adequately fastened.

- Make sure the condensing unit is clean and in

good working order; verify the absence of rust
or corrosion on components under pressure
and electrical connections.

- Make sure the refrigerant charge is suitable for

both winter and summer operation.

• Ensure that periodic in-service inspections
required by local regulations are performed.

13 - Replacement

Precaution must be taken when disconnecting

any components, cutting or drilling holes in the
tubing to ensure that no refrigerant under pressure
is present in the system.

The refrigerant shall not be discharged directly

into the atmosphere; rather, it must be removed
using approved reclamation techniques and
equipment and then safely stored, inaccordance
with applicable legislation.

The presence of refrigerant vapor can displace

air and lead to suffocation. Proper ventilation
is mandatory at all times when servicing the
equipment.

A condensing unit component change must be

carried out in compliance with local regulations.

• Make sure that the main power supply has been
switched off.

• Before replacement, it is necessary to determine
the cause of failure and implement remedial
action. If such analysis and repair are not performed,
repetitive failure may occur. Note that an oil acidity
test always proves helpful indiagnosis when
undertaking compressor replacement.

• Check that the replacement component has the
same electrical and refrigeration performance
characteristics as the original one.

• Whenever piping needs to be modified, please
refer to the «

Safety measures prior to assembly

»

section.

• For further details on replacement steps,refer to
the previous sections of this manual.

Note:

In the event of compressor motor failure,

flush and clean the entire circuit before replacing
the compressor in order to remove acids and
contaminants. Systematically install a new filter
dryer on the liquid line. Prior to this step (if
necessary), run the system for at least 2 hours
with anti-acid cartridges (in such instances, the
installation of a suction filter might also be required).
After an operating period of approximately 2 weeks,
check the level of oil acidity. If the oil acid test
proves positive, drain and replace the oil, replace
the anti-acid liquid line filter dryer cartridges and
the suction filter previously installed. Repeat oil
and filter dryer replacements until the system is
clean and acid-free.
When there is no longer any sign of acidity, replace
the anti-acid cartridges by the standard model and
remove the suction strainer cartridge as required.

14 - User advisory 

Insist that all service operations only be
performed by qualified personnel.

The condensing unit  tubing and compressor

surface temperatures may exceed 100°C (212°F)
and cause severe bodily burns. Special precaution
must be taken when working around the compressor
and refrigerant tubing. Moreover, a compressor
in operation can generate very cold surface
temperatures (as low as -45°C / -49°F), there by
exposing personnel to the risk of freezing burns.

Pressure inside the compressor and refrigerant

circuit can reach dangerously high levels (e.g.
abnormal operation, fire,…) leading to personnel
injury if suddenly released; therefore, never drill,
weld or cut the compressor shell and adjacent
tubing (release of liquid refrigerant can cause
flash freezing on exposed skin).

Even though fans are fitted with safety guard

it is recommended not to work on condenser
while fans are running.

Be aware that the product warranty may be
deemed null and void in the following cases:

• Modifications to the unit, unless approved by
Danfoss Commercial Compressors, absence of
nameplate, broken or dented components, shock
marks, etc...

• Compressor opened by the customer or returned
unsealed (i.e. open discharge or suction ports),

• Presence of rust or water inside the condensing
unit circuit,

• Addition of leak-detection fluid in the compressor
lubricant,

• Use of a refrigerant or lubricant not approved by
Danfoss Commercial Compressors.,

• Any deviation from recommended instructions
pertaining to installation, application or maintenance,

• Use in mobile applications (boats, trains, trucks,
etc.) or under explosive atmospheric conditions.

The date of production of the condensing unit is
indicated on the nameplate. Ensure that the model
and serial number information is always transmitted
with any claim filed regarding this product.

Instructions

6

8510198 P03-A     © Danfoss Commercial Compressors 03/05

Содержание Bluestar MGM016

Страница 1: ...MTZ65 MCZC121 MTZ73 MCZC136 MTZ81 900 900 759 MCZC171 MTZ100 MGZC215 MTZ125 MGZC242 MTZ144 1350 820 759 MGZC271 MTZ160 50 Hz Comp W D H ressor LCHC048 NTZ048 500 620 451 LCHC068 NTZ068 LCHC096 NTZ096...

Страница 2: ...2 8510198 P03 A Danfoss Commercial Compressors 03 05 Fig 4 Fig 3 Fig 5 1 x coil height Min clearance 2 x unit length Fig 2 Fig 6...

Страница 3: ...61 060 1263 060 1283 LP man LP auto LP auto LP man HP man HP man HP auto HP auto LP aut reset LP man reset HP AC1 16 A DC 11 LR 112A AC3 16 A 400 V 12 W AC1110 A 220 V When used acc to UL regulations...

Страница 4: ...condensing unit must be located in a well ventilated area air flow through unit shall not be restricted in any way refer to Fig 2 Make sure that the ambient temperature never exceeds 50 C 122 F during...

Страница 5: ...5 and 6 for typical wiring connections and examine the specific wiring diagram located in the electrical box cover For further details refer to the condensing unit guidelines Note that Maneurop compr...

Страница 6: ...s proper voltage balance between phases Change the filter dryer when necessary Check that all electrical connections are still adequately fastened Make sure the condensing unit is clean and in good wo...

Страница 7: ...MTZ81 900 900 759 MCZC171 MTZ100 MGZC215 MTZ125 MGZC242 MTZ144 1350 820 759 MGZC271 MTZ160 50 Hz Comp L P H resseur LCHC048 NTZ048 500 620 451 LCHC068 NTZ068 LCHC096 NTZ096 630 650 605 LCHC108 NTZ108...

Страница 8: ...8 8510198 P03 A Danfoss Commercial Compressors 03 05 8 12 m s capacit minimun 8 12 m s capacit maximun Fig 4 Fig 3 Fig 5 1 x hauteur de batterie Espace minimum 2 x longueur Fig 2 Fig 6...

Страница 9: ...declenchement Differentiel Differentiel fixe Point de renclenchement Test manuel Point de declenchement Couple de serrage 20 Nm Fil de cuivre uniquement Point de renclenchement Reset manuel Reglage d...

Страница 10: ...e au transporteur Les m mes recommandations s appliquent aux cas de non respect des instructions de transport Veuillez lire soigneusement les consignes de s curit imprim es sur l emballage carton ava...

Страница 11: ...s bobinages du moteur Ne pas utiliser d additifs pour la d tection des fuites Ne pas utiliser de CFC HCFC comme fluide traceur de d tection des fuites dans le cas d installations pr vues pour HFC 6 Ti...

Страница 12: ...limites d application du compresseur doivent tre respect es En outre des valeurs lev es de surchauffe conduisent des hautes temp ratures de refoulement et font diminuer la capacit du compresseur La t...

Страница 13: ...ous r f rer au chapitre Mesures de s curit avant montage Pour de plus amples renseignements sur les proc dures de remplacement se reporter aux chapitres pr c dent Note En cas de panne moteur du compre...

Страница 14: ...MTZ125 MGZC242 MTZ144 1350 820 759 MGZC271 MTZ160 50 Hz Verdi L B H chter LCHC048 NTZ048 500 620 451 LCHC068 NTZ068 LCHC096 NTZ096 630 650 605 LCHC108 NTZ108 LCHC136 NTZ136 755 700 656 LCHC215 NTZ215...

Страница 15: ...L fter f r Optyma Verfl ssigungss tze Zwei L fter f r Bluestar Verfl ssigungss tze Ein oder zwei L fter f r Optyma Verfl ssigungss tze Zwei L fter f r Bluestar Verfl ssigungss tze Abb 4 Abb 3 Abb 5 1...

Страница 16: ...konformem Einsatz 1 bar Pe 30in Hg KP 15 15A 17W 17B KP17W B 060 539366 060 539466 ND auto ND auto HD man HD auto Einschalten ND HD ND HD Differenz Feste Differenz Ausschalten Manueller Test Einschal...

Страница 17: ...sigungssatzes mit u erster Sorgfalt erfolgen sollen um St e und damit u erliche aber auch innere Besch digungen zu vermeiden F r die Handhabung und beim Auspacken sind geeignete und sichere Hebewerkze...

Страница 18: ...Durchf hrung des Lecktests getrost geschlossen gehalten bleiben jeder Verfl ssigungssatz wird bereits im Werk 100 auf etwaige Leckagen getestet Beim Auftreten einer Leckage sollte diese beseitigt und...

Страница 19: ...Verfl s sigungssatz Ein Niederdruckschalter wird empfohlen um Betrieb unter Vakuum vorzubeugen Eine Mindesteinstellung von 1 2 bar absolut ist als Faustwert angesehen werden Es ist daf r zu sorgen das...

Страница 20: ...falls zu ermitteln und deren Behebung zu veranlassen Wird diese Analyse und Reparatur nicht vorgenommen k nnen sich Ausf lle wiederholen Bitte beachten dass sich bei der Diagnose zum Austausch des Ver...

Страница 21: ...Z100 MGZC215 MTZ125 MGZC242 MTZ144 1350 820 759 MGZC271 MTZ160 50 Hz Spr arka S D W LCHC048 NTZ048 500 620 451 LCHC068 NTZ068 LCHC096 NTZ096 630 650 605 LCHC108 NTZ108 LCHC136 NTZ136 755 700 656 LCHC2...

Страница 22: ...ss Commercial Compressors 03 05 22 Tlumik wibracji 8 do 12 m s przy minimalnej wydajnosci 8 do 12 m s przy maksymalnej wydajnosci Fig 4 Fig 3 Fig 5 1 x wysoko wymiennika Minimalny odst p 2 x szeroko a...

Страница 23: ...5 15A 17W 17B KP 17B 060 539366 060 539466 LP auto LP auto HP man HP auto Ci nienie za czania R nica Sta a r nica Ci nienie wy czania Sprawdzian manualny Ci nienie za czania Tightening torque 20 lb in...

Страница 24: ...wania czy te produktu zauwa one przy dostawie powinny by niezw ocznie zg oszone przewoz nikowi Te same zalecenia odnosz si do przypadku gdy wykryte zostan uchybienia podczas transportu produktu do u y...

Страница 25: ...ponowi zgodnie z procedur tj pkt 1 i 2 5 pod czy spr ark do uk adu poprzez otwarcie zawor w odcinaj cych spr arki 6 powt rzy kroki 1 i 2 przy otwartych zaworach odcinaj cych na spr arce 7 wype ni inst...

Страница 26: ...minimum 12 godzin poprzedzaj ce rozruch i lub podczas d u szych okres w postoju 10 Uruchomienie Zabrania si za czania spr arki je eli nie jest ona nape niona czynnikiem ch odniczym Nie nale y boczniko...

Страница 27: ...ych w punkcie 3 rodki bezpiecze stwa podj te przed monta em urz dzenia Wprzypadkukonieczno ciwymianyelement w uk adu nale y stosowa si do szczeg owych zalece podanych we wcze niejszych punktach Uwaga...

Страница 28: ...rks of Danfoss A S All rights reserved Danfoss Commercial Compressors BP 331 F 01603 Tr voux France T l 04 74 00 28 29 33 4 74 00 28 29 Fax 04 74 00 52 44 33 4 74 00 52 44 http cc danfoss com Gdynia t...

Отзывы: