
© Danfoss 05-2011
AK-EM 100 Installation Guide
9
RC8BX402
3. Press the ‘Delete’ button to remove the gateway.
4. The next dialogue box will ask if you are sure you want to delete the gateway.
5. Press ‘OK’ to remove it.
If a gateways has been previously connected and the network uploads have been setup, then all of this
data will be removed.
When first viewed, the Network Communication section will look empty, because no network discoveries
or data runs have been initiated.
1.4.1 Network Upload
The first stage (once the Network Details have been correctly entered) is to perform a network discovery,
which will determine what controllers are available in the Gateway.
1. To begin the discovery, press the ‘Start’ button for
Network Upload
. In the new dialogue box, press
the ‘Confirm’ button to continue. The Assets will then begin to be displayed in the new window. When
complete, you will be presented with the choice of either ‘Accept’ or ‘Reject’ buttons. Checking the
‘Auto Accept’ box will bypass this section.
2. Press the ‘Accept’ button to add the assets to the Network list.
3. Wait until the
Network Upload
is complete; this will take some time depending on the amount of
assets attached to the controller. The status will change to
Stopped
and assets will be displayed in the
Network list table.
1.4 Network
Communications