Troubleshooting by Indication on the Remote Controller
SiUS34-907
146
Troubleshooting
3.21
“
H9
”
Malfunction of Thermistor (R1T) for Outdoor Air
Remote
Controller
Display
H9
Applicable
Models
RXYMQ36 · 48PVJU
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outside air temperature thermistor has short circuit or open circuit in operation
Supposed
Causes
Defective thermistor connection
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PCB (A1P)
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.241.
Replace the thermistor (R1T).
Resistance
is normal
w
hen
meas
u
red after disconnecting
the thermistor (R1T) from
the o
u
tdoor
u
nit PCB.
(3.5k
W
to
360k
W
)
Connector is
connected to X11A of o
u
tdoor
PCB (A1P).
Replace the o
u
tdoor
u
nit PCB
(A1P).
N
O
Connect the connector and t
u
rn
on again.
N
O
YES
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting the connector, or parts may
b
e damaged.
Confirm
w
hich thermistor is a
b
normal
u
sing o
u
tdoor
u
nit " monitor mode".
(Refer to P.105, 106)
YES
Содержание VRV III-S RXYMQ36 48PVJU
Страница 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Страница 9: ...SiUS34 907 Safety Considerations viii...
Страница 14: ...SiUS34 907 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 7...
Страница 37: ...Refrigerant Circuit SiUS34 907 28 Refrigerant Circuit S1PH S1NPH C 3D065366 A P G N M O H F S E T D D S1NPL...
Страница 232: ...SiUS34 907 Piping Diagrams Appendix 223 1 Piping Diagrams 1 1 Outdoor Unit RXYMQ36 48PVJU C 3D65366 S1NPL S1PH S1NPH...
Страница 236: ...SiUS34 907 Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ36 48PVJU 3D065263...
Страница 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Страница 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Страница 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Страница 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Страница 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Страница 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Страница 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Страница 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 247: ...Option List SiUS34 907 238 Appendix...
Страница 249: ...Example of Connection 240...
Страница 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...