Outline of Control (Indoor Unit)
SiUS34-907
50
Function
6.3
Thermostat Sensor in Remote Controller
Temperature is controlled by both the thermostat sensor in remote controller and air suction thermostat in the
indoor unit. (This is however limited to when the field setting for the thermostat sensor in remote controller is set
to “Use.”)
Note:
When OA (outdoor air) is introduced to the airconditioner with mixed into indoor air, the room temperature may
fail to be preset temperature, since TS and TH1 do not enter the area of “use range of remote control
thermostat.” In such a case, put the remote sensor (optional accessory) in your room, and use it with setting “do
not use remote control thermostat.”
Cooling
If there is a significant difference in the preset temperature and the suction temperature, fine adjustment control
is carried out using a body thermostat sensor, or using the sensor in the remote controller near the position of the
user when the suction temperature is near the preset temperature.
Ex: When cooling
Assuming the preset temperature in the figure above is 75°F, and the suction temperature has changed
from 64°F to 86°F (A
→
F):
This example also assumes there are several other air conditioners, the VRV system is off, and that temperature
changes even when the thermostat sensor is off.
Body thermostat sensor is used for temperatures from 64°F to 73°F (A
→
C).
Remote controller thermostat sensor is used for temperatures from 73°F to 81°F (C
→
E).
Body thermostat sensor is used for temperatures from 81°F to 86°F (E
→
F).
And, assuming suction temperature has changed from 86
°
F to 64
°
F (F
→
A):
Body thermostat sensor is used for temperatures from 86°F to 77°F (F
→
D).
Remote controller thermostat sensor is used for temperatures from 77°F to 70°F (D
→
B).
Body thermostat sensor is used for temperatures from 70°F to 64°F (B
→
A).
Содержание VRV III-S RXYMQ36 48PVJU
Страница 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Страница 9: ...SiUS34 907 Safety Considerations viii...
Страница 14: ...SiUS34 907 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 7...
Страница 37: ...Refrigerant Circuit SiUS34 907 28 Refrigerant Circuit S1PH S1NPH C 3D065366 A P G N M O H F S E T D D S1NPL...
Страница 232: ...SiUS34 907 Piping Diagrams Appendix 223 1 Piping Diagrams 1 1 Outdoor Unit RXYMQ36 48PVJU C 3D65366 S1NPL S1PH S1NPH...
Страница 236: ...SiUS34 907 Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ36 48PVJU 3D065263...
Страница 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Страница 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Страница 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Страница 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Страница 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Страница 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Страница 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Страница 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 247: ...Option List SiUS34 907 238 Appendix...
Страница 249: ...Example of Connection 240...
Страница 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...