SiUS34-907
Field Setting
Test Operation
71
Group No. Setting Example
Caution
When turning the power supply on, the unit may often not accept any operation while "88" is displaying after all
indications were displayed once for about 1 minute on the liquid crystal display. This is not an operative fault.
3.1.8 Setting of Operation Control Mode from Remote Controller
(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting the functions of the
operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in
accordance with the combination conditions. (Refer to information in the next page.)
Centralized remote controller is normally available for operations. (Except when centralized monitor is
connected)
3.1.9 Contents of Control Modes
Twenty modes consisting of combinations of the following five operation modes with temperature and operation
mode setting by remote controller can be set and displayed by operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn on/off by centralized remote controller only.
(Cannot be turned on/off by remote controller.)
OFF control only possible by remote controller
Used when you want to turn on by centralized remote controller only, and off by remote controller only.
Centralized
Used when you want to turn on by centralized remote controller only, and turn on/off freely by remote
controller during set time.
Individual
Used when you want to turn on/off by both centralized remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn on/off by remote controller during set time and you do not want to start operation
by centralized remote controller when time of system start is programmed.
Centralized Remote
Controller
F1 F2
F1 F2
F1 F2
F1 F2
P1 P2
RC
RC
RC
RC
RC
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
No Remote Controller
Group Control by Remote Controller
(automatic unit address)
1-03
1-00
1-01
Main
Sub
1-02
1-04
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
Indoor/Outdoor Outdoor/Outdoor
Содержание VRV III-S RXYMQ36 48PVJU
Страница 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Страница 9: ...SiUS34 907 Safety Considerations viii...
Страница 14: ...SiUS34 907 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 7...
Страница 37: ...Refrigerant Circuit SiUS34 907 28 Refrigerant Circuit S1PH S1NPH C 3D065366 A P G N M O H F S E T D D S1NPL...
Страница 232: ...SiUS34 907 Piping Diagrams Appendix 223 1 Piping Diagrams 1 1 Outdoor Unit RXYMQ36 48PVJU C 3D65366 S1NPL S1PH S1NPH...
Страница 236: ...SiUS34 907 Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ36 48PVJU 3D065263...
Страница 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Страница 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Страница 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Страница 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Страница 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Страница 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Страница 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Страница 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 247: ...Option List SiUS34 907 238 Appendix...
Страница 249: ...Example of Connection 240...
Страница 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...