Field Setting
SiUS34-907
76
Test Operation
a. “Setting mode 1”
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ····················· Used to select COOL or HEAT by individual outdoor unit
(factory setting).
• COOL/HEAT selection (MASTER) ············Used to select COOL or HEAT by outdoor unit group with
the master unit.
• COOL/HEAT selection (SLAVE)················ Used to select COOL or HEAT by outdoor unit group with
the slave unit.
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Push the SET (BS2) button to set
the blinking of LED to any of
conditions shown on the right.
Push the RETURN (BS3) button to
determine the setting.
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
“Normally, “Setting mode 1” is set.
In case of other status, push MODE
(BS1) button one time and set to
“Setting mode 1”.
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Pushing the RETURN (BS3) button
will bring the system to the initial
state of "Setting mode 1".
h
h
h
h
h
h
l
h
h
h
l
h
h
h
l
h
h
h
h
h
h
k
ON
h
OFF
l
Blink
Procedure for checking check items
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
h
h
k
h
h
h
h
Setting (displaying) item
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
For selection by individual
outdoor unit (factory setting)
For selection in a batch of
outdoor unit group with master unit
For selection in a batch of
outdoor unit group with slave unit
Pushing the RETURN (BS3) button will return the system to the initial condition of
"Setting mode 1".
Current operating conditions
h
Normal
k
Abnormal
l
In preparation or in
check operation
Setting of COOL/HEAT selection
k h h
By individual outdoor
unit
h k h
In a batch of outdoor unit
group with master unit
h h k
In a batch of outdoor unit
group with slave unit
Low noise operating conditions
h
In normal operation
k
In low noise operation
Demand operating conditions
h
In normal operation
k
In demand operation
Содержание VRV III-S RXYMQ36 48PVJU
Страница 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Страница 9: ...SiUS34 907 Safety Considerations viii...
Страница 14: ...SiUS34 907 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 7...
Страница 37: ...Refrigerant Circuit SiUS34 907 28 Refrigerant Circuit S1PH S1NPH C 3D065366 A P G N M O H F S E T D D S1NPL...
Страница 232: ...SiUS34 907 Piping Diagrams Appendix 223 1 Piping Diagrams 1 1 Outdoor Unit RXYMQ36 48PVJU C 3D65366 S1NPL S1PH S1NPH...
Страница 236: ...SiUS34 907 Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ36 48PVJU 3D065263...
Страница 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Страница 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Страница 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Страница 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Страница 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Страница 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Страница 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Страница 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 247: ...Option List SiUS34 907 238 Appendix...
Страница 249: ...Example of Connection 240...
Страница 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...