Field Setting
SiUS34-907
82
Test Operation
3.2.2 Cool / Heat Mode Switching
There are the following 4 cool/heat switching modes.
Set cool/heat separately for each outdoor unit system by indoor unit remote controller.
Set cool/heat separately for each outdoor unit system by cool/heat switching remote controller.
Set cool/heat for more than one outdoor unit system simultaneously in accordance with unified master
outdoor unit by indoor unit remote controller.
Set cool/heat for more than one outdoor unit system simultaneously in accordance with unified master
outdoor unit by cool/heat switching remote controller.
Set Cool / Heat Separately for Each Outdoor Unit System by Indoor Unit Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PCB DS1-1 to IN (factory setting).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory setting).
<Set the master unit (= indoor unit having the right to
select the cooling/heating operation mode).>
In the case of wired remote controllers
• After the check operation,
“CHANGEOVER UNDER
CONTROL”
is flashing in all connected remote controllers.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation mode selector button in the remote
controller of the indoor unit selected as the master unit.
• In that remote controller,
“CHANGEOVER UNDER
CONTROL”
disappears. That remote controller will control
changeover of the cooling/heating operation mode.
• In other remote controllers,
“CHANGEOVER UNDER
CONTROL”
lights.
For the details, refer to the installation manual
supplied together with the indoor unit.
In the case of wireless remote controllers
• After the check operation, the timer lamp is flashing in all
connected indoor units.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation selector mode button in the remote
controller of the indoor unit selected as the master unit. A
“peep” sound is emitted, and the timer lamp turns off in all
indoor units.
• That indoor unit will control changeover of the cooling/
heating operation mode.
Содержание VRV III-S RXYMQ36 48PVJU
Страница 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Страница 9: ...SiUS34 907 Safety Considerations viii...
Страница 14: ...SiUS34 907 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 7...
Страница 37: ...Refrigerant Circuit SiUS34 907 28 Refrigerant Circuit S1PH S1NPH C 3D065366 A P G N M O H F S E T D D S1NPL...
Страница 232: ...SiUS34 907 Piping Diagrams Appendix 223 1 Piping Diagrams 1 1 Outdoor Unit RXYMQ36 48PVJU C 3D65366 S1NPL S1PH S1NPH...
Страница 236: ...SiUS34 907 Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ36 48PVJU 3D065263...
Страница 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Страница 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Страница 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Страница 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Страница 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Страница 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Страница 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Страница 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 247: ...Option List SiUS34 907 238 Appendix...
Страница 249: ...Example of Connection 240...
Страница 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...