![Daikin VRV III-S RXYMQ36 48PVJU Скачать руководство пользователя страница 225](http://html1.mh-extra.com/html/daikin/vrv-iii-s-rxymq36-48pvju/vrv-iii-s-rxymq36-48pvju_service-manual_4706317225.webp)
SiUS34-907
216
Troubleshooting
Check the Factors of Overheat Operation
Identify the defective points referring to the Fault Tree Analysis (FTA) as follows.
∗
1:Refer to “Low Pressure Protection Control” for hot gas bypass control.
∗
2:Refer to "Electronic Expansion Valve PI Control" for "subcooling electronic expansion valve control".
∗
3:“Superheating temperature control” in cooling mode is conducted by indoor unit electronic expansion valve.
(Refer to "Electronic Expansion Valve Control")
∗
4:Superheating temperature control in heating mode is conducted by outdoor unit electronic expansion valve (EVM).
(Refer to "Electronic Expansion Valve PI Control").
∗
5:Judgement criteria of superheat operation:
N
Suction gas superheating temperature: 18 degrees and over.
O
Discharge gas superheating temperature: 81 degrees and
over, except for immediately after starting and dropping control.
(Use the above stated values as a guide. Depending on the other conditions, the unit may be normal despite the values within the
above scope.)
CHECK 7
Irregular piping length
Bend/collapse
(Including moisture choke)
Stop valve is closed.
4 way switch valve is in the
middle position.
Leak from hot gas bypass
valve
Subcooling
motor
operated
valve failure
Control
failure
Defective valve coil
Defective control PCB
Defective valve body
Defective valve coil
Defective valve body
Defective low pressure
sensor
Defective thermistor for
suction pipe
Defective control PCB
Defective thermistor for
indoor unit gas pipe
Defective thermistor for
indoor unit liquid pipe
←
Check if coil resistance and insulation
are normal.
←
Check if coil resistance and
insulation are normal.
←
Check if the voltage property is
normal.
←
Check if the connector is connected properly.
Check if the thermistor resistance property
is normal.
←
Check if the piping temperature connected
to the 4 way switch valve is normal.
←
Check if the pressure value given by the
service checker corresponding to actual
measurement value by the sensor.
←
Check if coil resistance and insulation are
normal.
←
Check if the connector is connected properly.
Check if the thermistor resistance property is
normal.
←
Check if the connector is connected properly.
Check if the thermistor resistance property is
normal.
←
Check if the connector is connected properly.
Check if the thermistor resistance property is normal.
←
Check if coil resistance and insulation are
normal.
←
Check if the voltage property is normal.
←
Refer to
CHECK 8
←
Check if the pressure value given by the
service checker corresponding to actual
measurement value by the sensor.
←
Does the piping length fall in the permissible range?
←
Conduct visual checks.
←
Remove the moisture by vacuum break. (Refer to
CHECK 9
)
←
Check if the stop valve is open.
Faulty
discharge
pipe
temperature
control
Faulty hot
gas bypass
control
Hot gas circuit clogging
Defective solenoid
valve coil
Defective solenoid
valve body
Defective control PCB
Defective control
PCB
Defective valve coil
Defective low
pressure sensor
Defective subcooling
heat exchanger
outlet thermistor
Defective valve
body
Faulty
subcooling
electronic
expansion valve
control (EV2)
Superheat due to
shaft damage
Superheat due to
defective compressor
Indoor unit
electronic expansion
valve failure
Faulty control
Faulty control
Outdoor unit
electronic expansion
valve failure
Faulty of 4 way
switch valve
operation
[In cooling mode only]
(
∗
1)
(
∗
2)
Compressor
overheat
Refrigerant gas
shortage
Large resistance
of piping
Faulty
superheated
degree
control.
[In cooling mode]
When indoor unit
electronic
expansion valve
becomes too
narrow (
∗
3)
[In heading
mode]When
outdoor unit
electronic
expansion valve
becomes too
narrow (
∗
4)
Temperature
increase of
discharge
pipe
Содержание VRV III-S RXYMQ36 48PVJU
Страница 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Страница 9: ...SiUS34 907 Safety Considerations viii...
Страница 14: ...SiUS34 907 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 7...
Страница 37: ...Refrigerant Circuit SiUS34 907 28 Refrigerant Circuit S1PH S1NPH C 3D065366 A P G N M O H F S E T D D S1NPL...
Страница 232: ...SiUS34 907 Piping Diagrams Appendix 223 1 Piping Diagrams 1 1 Outdoor Unit RXYMQ36 48PVJU C 3D65366 S1NPL S1PH S1NPH...
Страница 236: ...SiUS34 907 Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ36 48PVJU 3D065263...
Страница 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Страница 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Страница 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Страница 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Страница 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Страница 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Страница 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Страница 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 247: ...Option List SiUS34 907 238 Appendix...
Страница 249: ...Example of Connection 240...
Страница 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...