![Daikin VRV III-S RXYMQ36 48PVJU Скачать руководство пользователя страница 180](http://html1.mh-extra.com/html/daikin/vrv-iii-s-rxymq36-48pvju/vrv-iii-s-rxymq36-48pvju_service-manual_4706317180.webp)
SiUS34-907
Troubleshooting by Indication on the Remote Controller
Troubleshooting
171
3.35
“
P4
”
Malfunction of Inverter Radiating Fin Temperature
Rise Sensor
Remote
Controller
Display
P4
Applicable
Models
RXYMQ36 · 48PVJU
Method of
Malfunction
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction Decision Conditions:
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status
Malfunction is not decided while the unit operation is continued.
"
P4
" will be displayed by pressing the inspection button.
Supposed
Causes
Defect of radiator fin temperature sensor
Defect of main PCB (A1P)
Faulty inverter compressor
Faulty fan motor
Troubleshooting
Replace the main PCB (A1P).
Is the
thermistor resistance
v
al
u
e normal?
N
O
Replace the compressor (M1C).
YES
Replace the fan motor.
YES
Contin
u
e operation.
N
O
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting the connector, or parts may
b
e damaged.
Meas
u
re resistance
v
al
u
e of the
radiation fin thermistor. *
* Disconnect the connector (X111A) from the fin
thermistor, and then check the thermistor.
YES
The I
NV
.
compressor
'
s ins
u
lation
resistance is not more
than 100k
W
.
N
O
The fan
motor
'
s ins
u
lation
resistance is not more
than 1M
W
.
Replace the main PCB (A1P).
YES
Does the
malf
u
nction rec
u
r
w
hen
the po
w
er s
u
pply
t
u
rns O
N
?
N
O
Содержание VRV III-S RXYMQ36 48PVJU
Страница 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Страница 9: ...SiUS34 907 Safety Considerations viii...
Страница 14: ...SiUS34 907 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 7...
Страница 37: ...Refrigerant Circuit SiUS34 907 28 Refrigerant Circuit S1PH S1NPH C 3D065366 A P G N M O H F S E T D D S1NPL...
Страница 232: ...SiUS34 907 Piping Diagrams Appendix 223 1 Piping Diagrams 1 1 Outdoor Unit RXYMQ36 48PVJU C 3D65366 S1NPL S1PH S1NPH...
Страница 236: ...SiUS34 907 Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ36 48PVJU 3D065263...
Страница 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Страница 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Страница 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Страница 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Страница 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Страница 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Страница 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Страница 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 247: ...Option List SiUS34 907 238 Appendix...
Страница 249: ...Example of Connection 240...
Страница 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...