SiBE18-821_C
Method of Replacing Inverter’s Power Transistors Modules
Troubleshooting
431
Power module checking
When using the digital type of multiple tester, make measurement in diode check mode.
*There needs to be none of each value variation.
The following abnormalities are also doubted besides the PCB abnormality.
h
Defective compressor (ground fault, ground leakage)
h
Defective fan motor (ground leakage)
Tester terminal
Criterion
Remark
+
–
C+
U
Not less than 0.3 V
(including
∞
)*
It may take time to
determine the voltage
due to capacitor
charge or else.
V
W
U
C–
Not less than 0.3 V
(including
∞
)*
V
W
U
C+
0.3 ~ 0.7 V
(including
∞
)*
V
W
C–
U
0.3 ~ 0.7 V
(including
∞
)*
V
W