Field Settings
SiBE18-821_C
138
Test Operation and Field Settings
Setting by push button switches
The following settings are made by push button switches on PCB.
(Factory setting)
There are the following 3 setting modes.
(1)
Setting mode 1 (H1P off)
Initial status (when normal) : Also indicates during “abnormal”.
(2)
Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
(3)
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Mode changing procedure
Mode changing procedure
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED indication
h
h
k
h
h
h
h
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
(R12946)
Setting mode 1
Monitor mode
H1P
Blinking
MODE
MODE
Off
H1P
Setting mode 2
MODE
On
H1P
Push the BS1 (MODE button) one time.
(Normal)
Push and hold the BS1
(MODE button) for 5 seconds.
Push the BS1 (MODE button)
one time.
Using the MODE button, the modes can be changed as follows.
(R12947)
Check item selection (Set)
Contents display
Monitor mode
Setting mode 1
(Initial condition)
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Setting item selection (Set)
Setting mode 2
(Set): Select mode with BS2 (SET button) in each selection step.
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Press BS1 (MODE button) one time.
Press BS1 (MODE button) one time.
Press BS1 (MODE button) one time.
Press BS1 (MODE button) for more than 5 sec.
Setting condition
selection (Set)
Setting condition
(Contents) display
(R12948)
Содержание Super Multi Plus E-Series BPMKS967B2B
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...