SiBE18-821_C
Field Settings
Test Operation and Field Settings
143
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Setting item 0 Display contents of “Various setting”
No.
Setting item
LED display
Data display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
Various setting
l h h h h h h
See below
1
Cool / heat unified address
l h h h h h k
Lower 6 digits
2
Low noise/demand address
l h h h h k h
3
Not used
l h h h h k k
4
AIRNET address
l h h h k h h
5
Number of connected indoor units
l h h h k h k
7
Number of connected zone units
(excluding outdoor and BS unit)
l h h h k k k
8
Number of outdoor units
l h h k h h h
11
Number of zone units (excluding
outdoor and BS unit)
l h h k h k k
Lower 6 digits
12
Number of terminal blocks
l h h k k h h
Lower 4 digits:
upper
13
Number of terminal blocks
l h h k k h k
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
l h h k k k h
Error code table
Refer to page
326.
15
Contents of malfunction (1 cycle
before)
l h h k k k k
16
Contents of malfunction (2 cycle
before)
l h k h h h h
20
Contents of retry (the latest)
l h k h k h h
21
Contents of retry (1 cycle before)
l h k h k h k
22
Contents of retry (2 cycle before)
l h k h k k h
25
Normal judgment of outdoor units
PCB
l h k k h h k
Lower 2 digits:
k h
Abnormal
h k
Normal
h h
Unjudgment
EMG operation /
backup operation
setting
ON
l h h k h h h
OFF
l h h h h h h
Defrost select setting
Short
l h h h k h h
Medium
l h h h l h h
Long
l h h h h h h
Te setting
H
l h h h h k h
M
l h h h h l h
L
l h h h h h h
Tc setting
H
l h h h h h k
M
l h h h h h l
L
l h h h h h h
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
Содержание Super Multi Plus E-Series BPMKS967B2B
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...