Field settings
ESIE04-01
4–34
Part 4 – Commissioning and Test Run
3
1
4
5
Graph 3
Target evaporating temperature control when "low humidity appli freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Change thermostat
control
In order to increase continuous operation of the unit in low latent heat applications and avoid the rise
of temperature after thermostat OFF, the thermostat control will be changed when using field settings
16(26)-2-03 & 16(26)-2-04.
Thermostat ON
P
∆
Trs
≥
0.5 °C (No change from standard setting)
Thermostat OFF
P
∆
Trs
≤
-2.0 °C for 5 minutes continuously.
P
∆
Trs
≤
4.5 °C
Remote controller setting temp.
Te target limitted
≤
20°C
(to protect the comp.)
Te (by LP sensor) target acceptable area
P
Indoor temp.
>
setting
→
Te target down
P
Indoor temp.
<
setting
→
Te target up
Te target limitted
≥
2°C
(not to freeze)
Freeze protection
(40min. integrated coil temp.
≤
-1°C)
Te target acceptable area
Te target
(°C)
Indoor Temp
(°C DB)
RZQ - Final.book Page 34 Wednesday, September 8, 2004 8:40 AM
Содержание RZQ71~125B7V3B
Страница 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Страница 2: ......
Страница 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Страница 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Страница 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Страница 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Страница 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Страница 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Страница 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Страница 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Страница 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Страница 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Страница 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Страница 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Страница 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Страница 370: ...Disassembly and Maintenance Outdoor Units ESIE04 01 5 16 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 476: ...Disassembly and Maintenance Indoor Units ESIE04 01 5 122 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 484: ...ESIE04 01 viii Index 3 1 4 5 ...