Outdoor Unit Functional Concept
ESIE04-01
2–46
Part 2 – Functional Description
3
1
2
4
5
3.3.4
High Pressure Protection Control
Outline
In order to prevent abnormal high pressures in the system and hence avoiding activation of the high
pressure safety device the below control function will be activated.
Details
The high pressure value will be calculated from the low pressure, power input and compressor
frequency.
P
HPS opens at : 40 bar (tolerance: +0 / -0.15)
P
HPS closes at : 30 bar (tolerance : +/- 0.15)
Flow chart
Parameters
Normal operation
OR
Hp > 3.53 MPa
15 times or
less stop-
ping in 200
minutes
Normal operation
Compressor operation
frequency B Hz
Compressor stop
Malfunction stop (E3 indication)
Malfunction stop (E3 indication)
Compressor stop
Compressor operation
frequency A Hz
Compressor operation
frequency –1 step/10 sec
Compressor operation
fre1 step/1 min
Compressor operation
fre1 step/5 min
Hp > 3.58 MPa
Hp > 3.43 MPa
OR
OR
&
&
Hp < 3.38 MPa
• Hp > 3.82Mpa
• HPS activates
• HPS activates
• Stopped 16 times in
200 minutes
Hp < 3.48 MPa
• HPS activates
• Hp > 3.82 MPa
for 1 minute
• HPS activates
• Stopped 16 times
in 200 minutes
(When cooling operation)
(When heating operation)
Hp < 3.29 MPa
• Hp < 3.24Mpa
• 30 sec elapsed
RZQ71B
RZQ100 ~125B
A Hz
79 Hz
62 Hz
B Hz
62 Hz
62 Hz
RZQ - Final.book Page 46 Wednesday, September 8, 2004 8:40 AM
Содержание RZQ71~125B7V3B
Страница 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Страница 2: ......
Страница 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Страница 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Страница 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Страница 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Страница 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Страница 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Страница 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Страница 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Страница 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Страница 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Страница 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Страница 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Страница 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Страница 370: ...Disassembly and Maintenance Outdoor Units ESIE04 01 5 16 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 476: ...Disassembly and Maintenance Indoor Units ESIE04 01 5 122 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 484: ...ESIE04 01 viii Index 3 1 4 5 ...