ESIE04-01
Field settings
Part 4 – Commissioning and Test Run
4–27
3
4
5
1
2.13.2 External activation from optional PCB
Graph
Silent operation can also be activated from the optional PCB.
Silent operation will start when the contact on LNOP-COM is closed and will remain active as long as
the contact is closed. No field setting on the outdoor unit or by remote controller is required.
Silent operation will be ended when the contact is re-opened.
Use of the KRP58M enables the use of an external time clock.
Capacity priority
Setting
Same as with the automatic control, priority for capacity can be set.Prioirity for capacity will be
activated by changing field setting 26-0-03 in combination with the closed contact on KRP58M.
Exceptions
The silent operation will be overruled in the following conditions:
P
Pump down residual operation
P
Startup control
P
Defrost operation
P
Oil recovery
Sound reduction
Power supply connector
(on outdoor PCB X77A)
Output on X801M = 12VDC, 12mA
Maximum wire length = 100 meter
Transmission connector
(on outdoor PCB X6A)
Description
Mode
First
Code
Second Code
01
02
03
04
Silent Operation
16(26)
0
Factory
---
Capacity
priority
---
71
100
125
Sound reduction
4 dBA
4 dBA
5 dBA
RZQ - Final.book Page 27 Wednesday, September 8, 2004 8:40 AM
Содержание RZQ71~125B7V3B
Страница 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Страница 2: ......
Страница 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Страница 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Страница 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Страница 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Страница 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Страница 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Страница 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Страница 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Страница 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Страница 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Страница 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Страница 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Страница 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Страница 370: ...Disassembly and Maintenance Outdoor Units ESIE04 01 5 16 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 476: ...Disassembly and Maintenance Indoor Units ESIE04 01 5 122 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 484: ...ESIE04 01 viii Index 3 1 4 5 ...