ESIE04-01
Outdoor Unit Functional Concept
Part 2 – Functional Description
2–53
3
2
4
5
1
Frequency
restriction in
cooling
Heating
High outdoor ambient (overload conditions):
In heating overload conditions, the outdoor fan speed will be adapted to secure the differential
pressure between high and low pressure.
Only the fan speed will be adapted in heating overload conditions.
No adjustments to the compressor frequency will be made.
Normal control
Used indoor unit
Wall mounted indoor
Other than wall mounted
indoor
---
Upper limit
frequency
Lower limit
frequency
71
109Hz
169Hz
38Hz
100
112Hz
164Hz
41Hz
125
139Hz
Upper limit
frequency
Lower limit
frequency
71
109Hz
48Hz
100
123Hz
62Hz
125
Upper limit
frequency
Lower limit
frequency
71
109Hz
62Hz
100
123Hz
62Hz
125
Normal operation
Outdoor unit fan
–1 step/30 sec
Outdoor unit fan
+1 step/30 sec
•Hp-Lp < 0.39MPa
•Compression ratio
< 1.8
•Hp > 3.43MPa
OR
OR
•LP<0.05MP
•&
•OR
•OR
•&
•&
•&
•HP < 2.75MPa
•Hp-Lp > 0.69MPa
•Compression ratio > 2.4
•Hp-Lp > 1.08MPa
•Compression ratio > 3.2
•Hp < 3.2MPa
•Outdoor unit fan = 8 step
•Hp-Lp > 0.59MPa
•Compression ratio > 2.2
•Hp < 3.33MPa
RZQ - Final.book Page 53 Wednesday, September 8, 2004 8:40 AM
Содержание RZQ71~125B7V3B
Страница 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Страница 2: ......
Страница 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Страница 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Страница 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Страница 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Страница 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Страница 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Страница 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Страница 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Страница 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Страница 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Страница 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Страница 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Страница 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Страница 370: ...Disassembly and Maintenance Outdoor Units ESIE04 01 5 16 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 476: ...Disassembly and Maintenance Indoor Units ESIE04 01 5 122 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 484: ...ESIE04 01 viii Index 3 1 4 5 ...