Error Codes: Outdoor Units
ESIE04-01
3–68
Part 3 – Troubleshooting
3
1
3
4
5
3.11
Malfunction of Outdoor Fan Motor Signal (
H7
)
Remote Controller
Display
H7
Method of
Malfunction
Detection
Detection of signal malfunction from outdoor fan motor.
Malfunction
Decision
Conditions
When malfunction signal is detected at the start of fan motor operation.
Supposed Causes
P
Malfunction of fan motor signal (circuit failure)
P
Disconnection, short of fan motor lead wire and coming off the connector
P
Faulty PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is the connector(*)
of fan motor
connected correctly?
NO
YES
YES
Is the resistance value
normal in above
connector check?
NO
Connect correctly.
Replace the fan motor.
Replace the PC board.
(S2588)
Check No. 9
Check the fan motor
connector
*Connector symbol of fan motor
0
Caution for service
If the outdoor fan rotates due to strong wind, voltage generates in main circuit capacitor.
To prevent electric shock, make sure the low voltage of main circuit (50 VDC or lower)
before carrying out troubleshooting. To prevent PC board from being damaged, touch
the earth connector in an electric parts box immediately before the inserting and
extracting the connector, which discharges the static from human body.
Disconnect the power supply
Model name
RZQ71
RZQ100 to 125
Connector symbol
X206A
X206A, X207A
RZQ - Final.book Page 68 Wednesday, September 8, 2004 8:40 AM
Содержание RZQ71~125B7V3B
Страница 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Страница 2: ......
Страница 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Страница 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Страница 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Страница 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Страница 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Страница 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Страница 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Страница 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Страница 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Страница 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Страница 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Страница 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Страница 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Страница 370: ...Disassembly and Maintenance Outdoor Units ESIE04 01 5 16 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 476: ...Disassembly and Maintenance Indoor Units ESIE04 01 5 122 Part 5 Disassembly and Maintenance 3 1 5 5 ...
Страница 484: ...ESIE04 01 viii Index 3 1 4 5 ...