SiAF341904E
Outline of Control (Indoor Unit)
Part 4 Functions and Control
93
Note(s)
8. Outline of Control (Indoor Unit)
8.1 Set Temperature and Control Target Temperature
The relationship between remote controller set temperature and control target temperature is
described below.
Examples are given to illustrate a control target temperature that satisfies the remote controller
set temperature.
Regarding control target temperature
When using the infrared floor sensor, the temperature around people will be treated as the
control target temperature for operation.
What is the temperature around people?
The temperature around people refers to the temperature of the living space, obtained from the
temperature around the ceiling and the temperature underfoot. The temperature is calculated
using the detected values of the suction air thermistor and the infrared floor sensor.
It is difficult to use only suction air temperature control for underfoot air conditioning.
8.2 Thermostat Control
8.2.1 Without Optional Infrared Presence/Floor Sensor
The thermostat ON/OFF condition is determined by the difference between the remote
controller set temperature and the actual detected room temperature (
1).
Normal operation
Cooling operation
Dry operation
When Tro < 24.5°C
When Tro ≥ 24.5°C
ΔT = Detected room temperature – Remote controller set temperature
Tro: Detected room temperature at the start of dry operation
Tr: Determined by the room temperature detected by the thermistor
1: The thermistor used to detect room temperature is according to the field setting 10 (20)-2.
Remote controller set temperat
u
re
Control target temperat
u
re
˚C
Temperat
u
re
Cooling
Thermostat OFF
Normal operation
(Thermostat ON)
Δ
T ≤
–1.0°C
Δ
T ≥
+
1.0°C
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0°C
Tr
>
Tro + 1.0°C
Thermostat OFF
Tr
<
Tro – 1.5°C
Tr
>
Tro + 0.5°C
Dry operation
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...