Field Settings for Outdoor Unit
SiAF341904E
142
Part 5 Field Settings and Test Operation
: Setting does not return to factory setting when exit mode 2. To cancel the function, change
setting manually to factory setting.
: Once function is activated “t
01
” appears. To stop current function, press
Return (BS3)
button
once.
For detailed description about each setting, refer to
Details of Setting Mode (m2)
on page 143.
Indication
bold
means factory setting.
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
41 Do not change contents.
2
.
4
1
—
—
—
—
42 Do not change contents.
2
.
4
2
—
—
—
—
43 Do not change contents.
2
.
4
3
—
—
—
—
44 Do not change contents.
2
.
4
4
—
—
—
—
45 Do not change contents.
2
.
4
5
—
—
—
—
46 Do not change contents.
2
.
4
6
—
—
—
—
47 Do not change contents.
2
.
4
7
—
—
—
—
48 Do not change contents.
2
.
4
8
—
—
—
—
49 Outdoor > 50 m
above indoor
Height difference setting max. 90 m.
2
.
4
9
OFF (max. 50 m)
ON (max. 90 m)
0
1
50 Do not change contents.
2
.
5
0
—
—
—
—
51
Sequence multi
outdoor
Sequence addressing between master
and slave units.
2
.
5
1
Automatic
Forced master
Forded slave 1
Forced slave 2
0
1
2
3
76
VRTsmart
control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRTsmart
control.
2
.
7
6
Low 1
Low 2
Low 3
Low 4
Low 5
Low 6
Standard
High
0
1
2
3
4
5
6
7
78
VRT control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRT
control.
2
.
7
8
Standard
High
4
6
81
Cooling comfort
setting
Cooling comfort setting
2
.
8
1
ECO
Mild
Quick
Powerful
0
1
2
3
82 Do not change contents.
2
.
8
2
—
—
—
—
83 Master remote control setting when mix combination
2
.
8
3
VRV indoor
RA indoor
—
—
0
1
84 Do not change contents.
2
.
8
4
—
—
—
—
85 Do not change contents.
2
.
8
5
—
—
—
—
86 Do not change contents.
2
.
8
6
—
—
—
—
87 Do not change contents.
2
.
8
7
—
—
—
—
89 Do not change contents.
2
.
8
9
—
—
—
—
90
Indoor unit
without power
Possible for operate system when
some indoor units are temporary
without power supply.
2
.
9
0
Disabled
Enabled
0
1
95
Eco level setting for VRTsmart
2
.
9
5
Standard
Middle
High
0
1
2
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...