When the unit is equipped with an infrared presence/floor sensor:
: Factory setting
Refer to
Compensating the temperature around people
.
Note that the control is automatically switched to the one performed only by the suction air
thermistor for indoor unit when the Second code No. is
01
during the group control.
To use the remote controller thermistor during the group control, select the Second code No.
02
in First code No.
6
.
1.4.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
: Factory setting
"Filter Cleaning" is not displayed when an Auto-clean Panel is connected.
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
6
01
Remote controller thermistor control is not permitted during
group control
02
Remote controller thermistor control is permitted during group
control
Mode No.
Second Code No.
10 (20)
2
01
02
02
02
#
02
03
11 (21)
8
01
01
02
03
#
04
01
The thermistor to be used
Remote controller thermistor
—
—
—
—
Suction air thermistor
—
Infrared floor sensor
—
—
—
First Code No.
The infrared floor
sensor is not used
Priority given to
the suction air
temperature (
)
Only the remote
controller thermistor
is used
Priority given to the
floor temperature (
)
Only the suction air
thermistor is used
Standard setting
(Factory setting)
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...