SiAF341904E
Servicing Items to be Confirmed
Part 6 Service Diagnosis
161
(4) Precautions for outdoor unit multi system
All the settings should be made in the master unit. Settings in the slave units are deemed
unavailable.
Differentiation of Master/Slave Units
1. The outdoor unit master unit is the unit which has the connecting wires to the indoor unit. All
the other units are slave units.
2. You may also differentiate the master/slave units by the 7-segment display.
(5) Precautions for piping work and refrigerant charging:
This unit uses R-410A refrigerant. Pay attention to the following conditions.
1. The charging pipe and the manifold tube use R-410A products for pressure maintenance
and avoiding contamination by impurities (SUNISO oil, etc.).
2. Be sure to purge with nitrogen when brazing.
Properly perform airtightness test and vacuum drying. (Airtight test pressure: 4.0 MPa)
Charge refrigerant in liquid state.
(6) Precautions for operating in servicing mode (field setting):
When a test operation is interrupted or after exiting service mode, please wait for at least one
minute before entering service mode again. In case of continuous execution, the outdoor unit
PCB may sometimes display an error code. If any error codes are displayed, press the
RETURN
button (BS3). If performing the above operation still does not eliminate the error,
reconnect the unit to the power supply.
7-segment display
In normal mode, press the BS1 button once, and in
the confirmation mode, check if the 7-segment
display shows the code on the right.
SEG1
SEG2
SEG3
1
.
0
0
Press the confirmation button (BS3)
to check for the master/slave units
Master
0
Slave 1
1
Slave 2
2
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...