SiAF341904E
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
153
Setting of Demand Operation
By connecting the external contact input to the demand input of the external control adaptor for
outdoor unit (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
: However the demand operation does not occur in the following operation modes.
(1) Startup control
(2) Oil return operation
(3) Pump down residual operation
If carrying out demand or low noise input, connect the adaptor’s terminals as shown below.
A. When the demand operation is carried out by external contact (with the use of the
external control adaptor for outdoor unit).
1. Connect external control adaptor for outdoor unit and short circuit terminals as required
(Refer to the figure above).
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select a demand 1 level for the item 2-30.
B. When the constant demand operation is carried out. (Use of the external control
adaptor for outdoor unit is not required.)
1. While in setting mode 2, set the item 2-32 (Constant demand setting) to Level 1.
While in setting mode 2, select a demand 1 level for the item 2-30.
Setting content
Setting method
Set item
Condition
Content
External control adaptor
for outdoor
unit
Outdoor unit PCB
Demand 1
Level 1
The compressor operates at
60% or less of rating.
Short circuit "1" and
"C" on the terminal strip
(TeS1).
Set the item 2-32 to Demand 1, and the item
2-30 to Level 1.
Level 2
The compressor operates at
65% or less of rating.
Set the item 2-32 to Demand 1, and the item
2-30 to Level 2.
Level 3
The compressor operates at
70% or less of rating.
Set the item 2-32 to Demand 1, and the item
2-30 to Level 3.
Level 4
The compressor operates at
75% or less of rating.
Set the item 2-32 to Demand 1, and the item
2-30 to Level 4.
Level 5
The compressor operates at
80% or less of rating.
Set the item 2-32 to Demand 1, and the item
2-30 to Level 5.
Level 6
The compressor operates at
85% or less of rating.
Set the item 2-32 to Demand 1, and the item
2-30 to Level 6.
Level 7
The compressor operates at
90% or less of rating.
Set the item 2-32 to Demand 1, and the item
2-30 to Level 7.
Level 8
The compressor operates at
95% or less of rating.
Set the item 2-32 to Demand 1, and the item
2-30 to Level 8.
Demand 2
Level 1
The compressor operates at
40% or less of rating.
Short circuit "2" and "C".
Set the item 2-32 to Demand 2, and the item
2-31 to Level 1.
Level 2
The compressor operates at
50% or less of rating.
Set the item 2-32 to Demand 2, and the item
2-31 to Level 2.
Level 3
The compressor operates at
55% or less of rating.
Set the item 2-32 to Demand 2, and the item
2-31 to Level 3.
Demand 3
—
Forced thermostat OFF
Short circuit "3" and "C".
—
O
u
tside
w
iring indicated
b
y dotted line
External control
adaptor for
o
u
tdoor
u
nit
Host comp
u
ter
monitor panel
or demand
controller
X
X
X
X
F1
F2
P3
P4
F1
F2
P3
P4
X
X
X
X
X
X
1
2
3
C
Demand
Lo
w
noise
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...