SiAF341904E
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
151
2.8 Setting of Night-Time Low Noise Operation and Demand
Operation
Setting of Night-time Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external
control adaptor (optional), you can lower operating noise by 2-3 dB.
A. When night-time low noise operation is carried out by external contact (with the use of
the external control adaptor for outdoor unit)
1. Connect external control adaptor for outdoor unit and short circuit terminal of night-time low
noise operation (Refer below figure). If carrying out demand or low noise input, connect the
adaptor’s terminals as shown below. External control adaptor for outdoor unit Host computer
Outside wiring indicated monitor panel by dotted line or demand controller
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select an external low noise level for the item 2-25.
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If
the condition is set to ON, when the air conditioning load reaches a high level, the low noise
operation command will be ignored to put the system into normal operation mode.)
B. When night-time low noise operation is carried out automatically (External control
adaptor for outdoor unit is not required)
1. While in setting mode 2, select a night-time low noise operation level for the item 2-22.
2. If necessary, while in setting mode 2, select a starting time of night-time low noise operation
(i.e., 8:00 PM, 10:00 PM, or 12:00 AM) for the item 2-26. (Use the starting time as a guide since
it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select an ending time of night-time low noise operation
(i.e., 06:00 AM, 07:00 AM, or 08:00 AM) for the item 2-27. (Use the ending time as a guide since
it is estimated according to outdoor air temperatures.)
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If the
condition is set to ON, when the air conditioning load reaches a high level, the system will be put
into normal operation mode even during night-time.)
Setting
Content
Level 1
Set the outdoor fan to Step 7 or lower.
Level 2
Set the outdoor fan to Step 6 or lower.
Level 3
Set the outdoor fan to Step 6 or lower.
O
u
tside
w
iring indicated
b
y dotted line
External control
adaptor for
o
u
tdoor
u
nit
Host comp
u
ter
monitor panel
or demand
controller
X
X
X
X
F1
F2
P3
P4
F1
F2
P3
P4
X
X
X
X
X
X
1
2
3
C
Demand
Lo
w
noise
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...