Troubleshooting with Remote Controller
SiAF341904E
182
Part 6 Service Diagnosis
U1 - 16
Open phase for power supply (Master)
Refer to the
U1
flowchart and make a diagnosis based
on the Error code shown to the left.
U1 - 17
Open phase for power supply (Slave 1)
U1 - 18
Open phase for power supply (Slave 2)
U1 - 19
Hz error for power supply (Master)
U1 - 20
Hz error for power supply (Slave 1)
U1 - 21
Hz error for power supply (Slave 2)
U2 - 01
Shortage of inverter power supply voltage (Master)
Refer to the
U2
flowchart and make a diagnosis based
on the Error code shown to the left.
U2 - 08
Shortage of inverter power supply voltage (Slave 1)
U2 - 11
Shortage of inverter power supply voltage (Slave 2)
U2 - 22
Shortage of inverter 2 power supply voltage (Master)
U2 - 25
Shortage of inverter 2 power supply voltage (Slave 1)
U2 - 28
Shortage of inverter 2 power supply voltage (Slave 2)
U3 - 02
Initial installation alarm / Test operation failed due to
indoor unit error
Refer to the
U3
flowchart and make a diagnosis based
on the Error code shown to the left.
U3 - 03
Test operation not conducted
U3 - 04
Abnormal end of test operation
U3 - 05
Premature end of test operation during initial
transmission error – check indoor unit error U4 / U9
U3 - 06
Premature end of test operation during normal
transmission error
U3 - 07
Premature end of test operation due to transmission
error
U3 - 08
Premature end of test operation due to transmission
error of all units
U3 - 10
System refrigerant auto charge operation not yet
executed
U4 - 01
Transmission error between indoor unit and outdoor
unit
Refer to the
U4
flowchart and make a diagnosis based
on the Error code shown to the left.
U4 - 03
Transmission error between indoor unit and system:
check indoor unit error
U7 - 01
Error when external control adaptor for outdoor unit is
installed
Refer to the
U7
flowchart and make a diagnosis based
on the Error code shown to the left.
U7 - 02
Alarm when external control adaptor for outdoor unit is
installed
U7 - 03
Transmission error between master and slave 1 units
U7 - 04
Transmission error between master and slave 2 units
U7 - 05
Multi system error
U7 - 06
Error in address settings of slave 1 and 2
U7 - 07
Connection of four or more outdoor units in the same
system
U7 - 11
Error in indoor unit connection capacity for test
operation
U9 - 01
Other indoor units and outdoor unit abnormality
Refer to the
U9
flowchart and make a diagnosis based
on the Error code shown to the left.
UA - 00
TSS plus unit field settings error, CT
address duplication warning
Refer to the
UA
flowchart and make a diagnosis based
on the Error code shown to the left.
UA - 03
Connection of excessive indoor units
UA - 17
Connection of excess indoor units
UA - 18
Connection of incorrect models of indoor units
UA - 20
Improper combination of outdoor units
UA - 21
Wrong connection
UA - 31
Multi system combination error
UF - 01
Wrong wiring check error
Refer to the
UF
flowchart and make a diagnosis based
on the Error code shown to the left.
UF - 05
Defective stop valve for test operation
UH - 01
Wiring error
Refer to the
UH
flowchart.
Error code
Troubleshooting
Description of error
Diagnosis
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...