SiAF341904E
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
145
m2-26:
Start time automatic night-time low noise
operation. When the auto night-time low
noise operation is active (refer to field setting 2-22) outdoor will start when start time is
reached time is reached. The time judgement is taken from outdoor air tendency.
Default value: 2 (10:00 PM)
Field setting 1: 8:00 PM, 3: 12:00 AM (midnight).
m2-27:
Stop time automatic night-time low noise
operation. When the auto night-time low
noise operation is active (refer to field setting 2-22), outdoor unit will stop the night-time low
noise operation level automatically when stop time is reached.
Default value: 3 (8:00 AM)
Field setting 1: 6:00 AM, 2: 7:00 AM
m2-28:
Power transistor check
mode. To evaluate the output of the power transistors. Use
this function in case error code is displayed related to defective inverter PCB or inverter
compressor is locked.
Default value: 0. Power transistor check mode is not active.
Field setting 1: Power transistor check mode is active.
Function:
Inverter PCB gives output of 10 Hz in sequence by all 6 transistors. Remove the U/V/
W terminals of the inverter compressor, and connect to the inverter checker module.
If all 6 LEDs blink, the transistors switch correctly.
When the power transistor check mode is interrupted, after internal power circuit is
disconnected on the inverter PCB, 2 LEDs will light up to indicate discharge of the DC
voltage.
Wait until the LEDs are OFF before returning fasten terminals back to the compressor
terminals.
Minimum requirements to refer to the result on the inverter checker module:
All 3 phases and neutral are available, and
Inverter PCB control is active. Check if the green LED “HAP” on the inverter PCBs are
blinking normal (approx. 1/ second). If LEDs are OFF, need to exit the “standby
mode” of the inverter:
Disconnect and reconnect power supply control PCB, or
Forced thermostat ON condition, or
Make shortly set 2-6-1 (forced thermostat ON indoor), or
2-20-1 (manual refrigerant charge).
Once the LED is blinking on the inverter PCB, change related setting immediately
back to set 0 to deactivate related function.
Diode module generates the required 500 VDC.
Cautions:
Capability%
Load%
100
50
0
*
W
hen the o
u
tdoor air temperat
u
re
b
ecomes highest,
the
u
nit is sensed as 2:00 PM
Max.
8
dB reduced
(10 HP)
50
5
8
8
:00 AM
12:00 PM
4:00 PM
8
:00 PM
12:00 AM
4:00 AM
8
:00 AM
Ni
g
ht mode
starts
Ni
g
ht mode
ends
Operation
sound dB
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...