Troubleshooting by Error Code
SiAF341904E
198
Part 6 Service Diagnosis
5.8 Humidifier System Abnormality
Applicable
Models
FXFSQ, FXMQ-PB
Error Code
AF
Method of Error
Detection
Water leakage from the humidifier system is detected based on float switch ON/OFF operation
while the compressor is not in operation.
Error Decision
Conditions
The float switch changes from ON to OFF while the compressor is not in operation.
Error code is displayed but the system operates continuously.
Supposed
Causes
Humidifier unit (optional accessory) leaking
Defective drain piping (upward slope, etc.)
Defective indoor unit control PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Defective indoor unit
control PCB (A1P).
Modify the drain piping.
YES
NO
NO
YES
Check if the humidifier unit is
leaking.
Field drain
piping has a defect such as
upward sloping.
A humidifier
unit (optional accessory) is
installed on the
indoor unit.
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...