Appendix
SiE33-003
94
General Information
7.2
Allowable Piping Length
Points of piping desigh
1. b + c = 100m
2. Level difference between outdoor units (Main and Sub units) a
≤
5 m
3. Piping distance between first branch and the farthest indoor unit
≤
40 m
4. Level difference between indoor units
≤
15 m
5. Level difference between indoor and outdoor unit
≤
50 m
(Level difference is lower than 40 m when outdoor unit is installed below indoor unit.)
6. Refnet joint and header are not downstream for first installed Refnet header.
Si33-003.book Page 94 Monday, June 25, 2001 9:06 AM