Field Wiring
Installation Manual
155
7.6.4
Field Line Connection : Transmission Wiring and Cool/Heat Selection
7.6.5
Example of Performing Cool/Heat with Cool/Heat Selector
7.6.6
Example of Performing Cool/Heat Setting of Two or More Outdoor Units in Block with
Cool/Heat Selector
For the wiring shown in figure 22, be sure to use 0.75-1.25 mm
²
vinyl cords with sheath or cables (two-
core). (Three-core cables can be used only for the cool/heat selector.) (Insulated thickness : 1mm or
more)
The wires shown in figure 22 are field supply.
Caution
Be sure to follow the limits below. If the unit-to-unit cables are beyond these limits, it may result in
malfunction of transmission.
Maximum wiring length: 1000m
Total wiring length: 2000m
Max branches No. of branches: 16
Up to 16 branches are possible for unit-to unit cabling. No branching is allowed after branching.
Never connect the power supply to unit-to-unit cabling terminal block. Otherwise the entire system may
break down.
1. Switch box (Main unit)
2. Fix to the safety catch using the
attached clamp material
3. Attached cable (between main and
sub units)
A
B
C
F1
F2
F1
F2
RXYP 8,10,16,20
X2M
A1P
3
2
1
Fig. 21
(V0873)
1. Cool/Heat selector (optional for heat
pump unit only)
2. Outdoor unit P.C. Board (A1P)
3. Take care of the polarity
4. Use the conductor of sheathed wire
(2 wire) (no polarity)
5. Terminal board (Field supply)
6. Indoor unit
A B C
A B C F1
F1
F2
F2
A
B
C
F1
F1
F2
F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
4
5
6
1
2
C/H SELECTOR
TO IN/D UNIT TO OUT/D UNIT
TRANSMISSION WIRING
A1P
3
Fig. 22
(V0874)
1. Branch
2. Subbranching
1
2
Fig. 23
(V0875)
Si33-003.book Page 155 Monday, June 25, 2001 9:06 AM